Too high ambient
temperature
Check that the chiller is located in a place that can guarantee suitable
ventilation of the refrigerating unit. Check also that the ambient temperature
does not exceed +40°C.
Note: after solving the cause of
the fault, start the chiller by
pressing the reset button located
on the external body of the
pressure switch itself (see the
picture)
Possible corrective Action
The compressor works continuously and the chiller can’t control the liquid temperature:
- too low temperature of the liquid
- too high temperature of the liquid
Broken thermostat (contact blocked)
Not enough Freon in the unit
Please ask for the service by a refrigeration engineer
Possible wrong application, to be checked with our staff
Possible corrective Action
No flow rate in the circuit
Check the right rotation of the electrical motor