ON-LINE 1000VA / 2000VA / 3000VA
PH 9210 - PH 9220 - PH 9230 .
005
Converter
Mode
[DIS] (Disable) [ENA]
(Enable)
Disable
006
EPO/ROO***
[EPo] /[Roo]
EPO
007
EBM
Number****
[0bP]/[1bP]/[2bP]/[3bP]/[4bP
]/[5bP]
/[6bP]/[7bP]/[8bP]/[9bP]
/[AbP]
0(for standard
models)
/ 1 (for long-run
models)
008
Bypass when
UPS is Off
[DIS] (Disable) [ENA]
(Enable)
Disable
009
Buzzer
[DIS] (Disable) [ENA]
(Enable)
Enable
*) When operating in ECO Mode, the efficiency of UPS is higher than that in online mode,
but transfer time should not be 0ms
**) When operating in Converter Mode, the frequency of output should be always 50Hz or
60Hz, but load capacity will be derated by 40%.
*) This function would be set as 0% when Converter Mode is enabled.
**) UPS has no bypass when Converter Mode is enabled.
***) ROO (Remote On/Off): If ROO is enabled, UPS can be turn on/off by the ROO port. If
ROO port is disconnected, UPS will be turned off. If ROO port is connected, UPS will be turned
on when the utility is normal
****) 1. UPS cannot detect the numbers of external battery automatically, so
manual input from user is necessary.
2. For standard models, the maximum number is 3. For long run models, the maximum
number is 10. If EBM number is 1~3, the charge current will be 4A, if EBM number is 4 ~10, the
charge current will be 8A.