EasyManua.ls Logo

Phenix Technologies 600 SERIES - Page 9

Default Icon
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6CP100/50-10
3-3
CONTROLS AND INDICATORS
High Voltage Transformer
Figure 3-2
The following descriptions are keyed to Figure 3--2:
1. Power Connector
Connect the Power Cable from Output to Transformer connector on control box at this point.
2. High Voltage Unit Ground Point
A Ground cable from facility ground or earth ground must be connected here.
3. Guard Binding Post (GRD)
Currents associated with this connection bypass the current meter (meter bypass connection). See
Section 5 for more information on these connections.
4. Ground Binding Post with Jumper Clip (GND) - This binding post is connected to ground. See
Section 5 for more information on these connections.
NOTE: The Jumper Clip must always be connected from Ground to either Return or Guard.