PLC / Modbus/RTU
105542_en_05 PHOENIX CONTACT 75 / 198
6.6.6 RAD-DOR4-IFS process data
I/O module Module type ID Register Address range Function code
RAD-DOR4-IFS 10
hex
02
hex
40xx0 ... 40xx1
1
1
xx = I/O MAP address set using the white thumbwheel
fc 03, 16
Table 6-14 RAD-DOR4-IFS module type and timeliness of data
30xx0
1
1
xx = I/O MAP address set using the white thumbwheel
Module type and timeliness of data
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Y
2
2
Y = timeliness of data, bit 8
If the data in the register is not up to date, then the register value is 1. If the process data has been written
to one of the registers, then the register value is 0. The value then remains 0 for the entire operating time
of the device.
Module type
3
3
If the module type in the register is invalid or not available, then the register value is 0.
40xx1 Digital outputs
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
DO
4
DO
3
DO
2
DO
1
Terminal point
6.x 5.x 2.x 1.x
40xx2 ... 40xx9 Reserved