EasyManua.ls Logo

Phoenix Controls FSR100 - Troubleshooting Common Issues; No Signal Input Troubleshooting; Incorrect Output Troubleshooting

Phoenix Controls FSR100
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 OF 12—FAN STATIC RESET KIT MKT-0266 MPC-1480 ©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10
TROUBLESHOOTING
There is no signal input Check for power between the red and black wires
Power should be between 7 to 40 Vdc or 7 to 32 Vac
If no voltage is present check power source at the controller and interconnecting
cable
If voltage is present, disconnect all other devices from the controller to see if the
signal returns
Disconnect the white signal wire going to the controller and using a volt meter,
check for a signal voltage
If the device has a proper power source and there is no output signal with all other
devices disconnected, it must be returned to the factory for replacement.
The output signal appears to be
incorrect
With no differential pressure across the sensor, the output signal should be 0.25
Vdc ±0.06 Vdc
Disconnect the tubing and connect a short piece of tubing across both the high
and low pressure ports to shunt the high and low to the same value. The voltage
output should be 0.25 Vdc
- If the signal is 0.25 Vdc but the pressure variable does not read 0, make
sure the scaling in the Configuration Plug-in indicates 0.25 Vdc = 0" W.C.
- If the zero output has shifted, there are no user adjustments on the sensor
itself so the Configuration Plug-in must be used to rescale the input voltage
(ex. 0.45 Vdc = 0" W.C.)
With differential pressure across the sensor if you suspect the signal is reading
incorrectly
There is no span adjustment on the pressure sensor. If a duct traverse indicates
there is an error, the only option is to use the Configuration Plug-in to adjust the
scaling of the input voltage range. For example, if 0" W.C. is at 0.45 Vdc and 5"
W.C. is at 4.75 Vdc, the Configuration Plug-in scaling needs to indicate 0.45
Vdc = 0" W.C. and 4.75 Vdc = 5" W.C.