12 OF 12—FAN STATIC RESET KIT MKT-0266 MPC-1480 ©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10
1
Load is 96 VA when power is provided by a 100 VA transformer with external 4 amp slow blow fuse.
2
Load is 100 VA when power is provided by a 100 VA transformer with internal circuit breaker.
MS/TP Specifications for Alternate Cable Solutions
1. An MS/TP EIA-485 network shall use shielded, twisted-pair cable with characteristic impedance between 100 and 130Ω.
2. Distributed capacitance between conductors shall be less that 100 pF per meter (30 pf per foot).
3. Distributed capacitance between conductors and shield shall be less that 200 pF per meter (60 pF per foot).
4. Foil or braided shields are acceptable. The maximum recommended length of an MS/TP segment is 1200 meters (4000 feet)
with AWG 18 (0.82 mm
2
conductor area) cable.
5. The use of greater distances and/or different wire gauges shall comply with the electrical specifications of EIA-485 for MS/TP
cable requirements.
4C
MS/TP
Ye s A r m o r e d
Shielded
22 Belden 1269A
(100 ohm)
See specifications
below for alternate
cable solutions
1: Red
2: Blue
3: Black
4: Yellow
Foil and
braided
shield with
drain
4C
MS/TP
Ye s A r m o r e d
Shielded
22 Belden 123107A
(100 ohm)
See specifications
below for alternate
cable solutions
1: White with Blue stripe
2: Blue with White stripe
3: White with Orange stripe
4: Orange with White stripe
Foil and
braided
shield with
drain
4C
MS/TP
Ye s A r m o r e d
Shielded
24 Belden 82842
(100 ohm)
See specifications
below for alternate
cable solutions
1: White with Blue stripe
2: Blue with White stripe
3: White with Orange stripe
4: Orange with White stripe
Foil and
braided
shield with
drain
Low smoke
4C
MS/TP
Yes Shielded 24 Belden 82729
(100 ohm)
See specifications
below for alternate
cable solutions
1: White with Blue stripe
2: Blue with White stripe
3: White with Orange stripe
4: Orange with White stripe
Shield with
drain
4C
MS/TP
Yes Shielded 24 Belden 88102
(100 ohm)
See specifications
below for alternate
cable solutions
1: White with Blue stripe
2: Blue with White stripe
3: White with Orange stripe
4: Orange with White stripe
Shield with
drain
Cable
Type
Plenum
Rated
Function
Wire
Gauge
Primary
Vendor/Part #
Alternate
Vendor/Part #
Color Code Notes