8 OF 12—FAN STATIC RESET KIT MKT-0266 MPC-1480 ©2010 Phoenix Controls Specifications subject to change without notice. Rev. 5/10
At the Celeris Pneumatic or Low-Speed Electric, or LON TP/SO Controller
• FSR power wire terminates on TB4, Terminal 1 (L1)
• FSR signal "+" wire terminates on TB1, Terminals 1, 3 or 5 (+)
• FSR circuit common wire terminates on TB1, Terminals 2, 4 or 6 (-)
NOTE: A jumper wire must be added between the circuit common termination and TB4, Terminal 2 (L2)
Celeris pneumatic, or low-speed electric, or LON TP/SO: any available UI (1, 2 or 3)
At the LON TX controller
• FSR power wire terminates on TB4, Terminal 1 (L1)
• FSR signal "+" wire terminates on TB1, Terminals 1, 3 or 5 (+) or TB8, Terminals 1 or 3 (+)
• FSR circuit common wire terminates on TB1, Terminals 2, 4 or 6 (-) or TB8, Terminals 2 or 4 (-)
NOTE: A jumper wire must be added between the circuit common termination and TB4, Terminal 2 (L2).
LON TX: any available UI (see LON TP/SO for 1, 2 or 3; see below for 4 or 5)
+ 1
- 2
UI1
TB1
-
4
5
+
UI3
UI2
3
+
-
6
-
8
DI1
+
7
L2
L1
GND
WHITE (SIGNAL)
BLACK (CIRCUIT COMMON)
RED (POWER)
JUMPER WIRE
TB4
+
-
UI4
TB1
-
UI5
+
L2
L1
GND
WHITE (SIGNAL)
BLACK (CIRCUIT COMMON)
RED (POWER)
JUMPER WIRE
TB4