INSTALLATION GUIDE
SET THE DIP SWITCHES ON THE ADJUSTMENT BOARD
DESCRIPTION
ON
OFF
Closed Door Force
Additional
force applied while door is in
closed
position
. Be sure to maintain ANSI
compliance
if
using on low energy application.
Cannot
exceed
30 lbf to get door moving from jamb.
Disabled (Default)
Push / Pull Arm
Slide
Arm Application. Operator stroke at 90
°
degrees
or less. Visible change in
performance
may
not always be noticeable.
Push Arm Application. Operator stroke 90
° or
greater. (Default)
Night Function (Exit
Only)
Allows
for one final activation at input 10
when
On
-Off switch is in OFF (night
function)
position
.
Disabled. The On/Off switch, when OFF, requires
manual operation of the door. (Default)
Push and Go
Enabled
Disabled (Default)
Full Power / Low
Energy
Low
Energy performance enabled. 5 seconds
to
open,
7 seconds hold open, 5 seconds to close
.
Speed
& time potentiometers are disabled
.
Settings
are fixed.
Disabled. Control can be adjusted for full power or
low energy operation via potentiometers. (Default)
Lockout Function
Overhead
presence sensor input (17)
is
inhibited
during closing cycle unless input 14
is
triggered
. Connect COM and Input 14 to
NC
output
of lockout safety beam.
Disabled. Overhead presence sensor input (17) is
inhibited during closing cycle. Otherwise, if
commanded, it keeps an open door open and a
closed door closed. A command at Input 14 will stall
the door. (Default).
Inhibit at 30 Degrees
Before Door Fully
Open
Input
is disabled at 30 degrees prior to
full
open
door position. Eliminates need
for
external
inhibiting switch.
Stall function remains un
-inhibited for full door
stroke. (Default)
Power Close
Additional
closing force applied for final
10
degrees
of closing.
Disabled (Default)
Assisted Manual
Closing
***
Enabled
assisted closing following a
manual
opening
Disabled assisted closing following a manual opening
FACTORY USE ONLY
*** PORTALP USA, Inc. recommends the use of a door-mounted secondary activation device when dip switch 9 is ON - Enabled.
WWW.PORTALP.COM | 27
Automatic Doors & Building Access Control
SW10 (Full Power) & SW19 (Low Energy)