INSTALLATION GUIDE
LOW ENERGY APPLICATION: PUSH PLATES WITH APPROACH SIDE DOOR-MOUNTED SENSOR
§ Non-Swing Side (approach) door-mounted sensor is wired into the secondary activation input (13)
at the I/O board. It is a normally closed circuit. Remove factory jumper on terminal 13.
§ Door-mounted sensor will cause re-activation when in detection during the closing cycle.
§ Secondary activation input is disabled at the full closed door position.
§ Jumpers must be installed between terminal 8 and 12 & 14 if those inputs are not required for the
application. If they are used for the application, they must be connected to a N.C. circuit.
APPENDIX - WIRING DIAGRAMS