PFC-6006
Conventional Fire Panel
8830038 - REV E • 4/19 PAGE 1 OF 2
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
Features
• 6 Programmable Initiating Device Circuits
• ClassAorClassBWaterowInitiatingCircuit
• 2 Wire Smoke Detector Compatibility
• 1.0AmpPowerSupply
• 1NoticationCircuitratedat0.5AmpsRegulated
• Strobe Synchronization for Potter/AMSECO, Gentex, System
SensorandCooper/Wheelock
• 0.5AmpAuxiliaryPower,ProgrammableasConstantor
Resettable
• 2x16LCDdisplaywithsystemLEDsforclearsystemstatus
• Keypadforsystemfeatures
• P-LinkforRemoteAnnunciatorConnections
• Capacitytochargeandhouse18AHbatteries
• OnboardDualLineDigitalAlarmCommunicator
• Built-inEthernetConnectionwithlistedIPCommunicator
• AbilitytoE-mailsystemstatus,reportsandsystemconguration
• ServiceReminderE-mails
General Description
ThePFC-6006isalistedsmallconventionalresystemideallysuited
tomonitorasmallresystemsuchasaresprinklersystem.Therst
inputisselectableasaClassAorClassBwaterowinputandtheother
vezonesareselectablefromamenuofoptionsincludingtwo-wire
smokedetection.Thepanelhasa1.0amppowersupplythatpowers
thepanel,chargesthebatteriesandsupplies0.5ampstoanotication
appliancecircuitand0.5ampsofauxiliarypower.Theauxiliarypower
is programmable as constant or resettable.
Thecontrolpanelisinametalcabinetwithakeylockandlexanwindow
forviewingthesystemstatus.Theprintedcircuitassemblyismounted
forquickremovalandinstallationtoallowthecabinettobeinstalledwith
minimaleffort.Thecabinethousesuptotwo12VDC,18AHbatteries.
Thedisplayisathirty-two(32)characterLCDwithsystemstatusLEDs.
Thesystemstatusisclearlydisplayedandthepanelincludesahistory
bufferforpastevents.Thekeypadallowsnavigationintothesystem
menu, limited programming and system control. The condition and
eventsonthepanelareclearlydisplayedtoallowtheuserandinstaller
todeterminethesystemstatus.
Thepanelhasadualtelephonelinedigitalalarmcommunicatortransmitter
(DACT)builton-board.Oneorbothtelephonelinesmaybeenabled
toallowcommunicationtoaremotemonitoringstation.Inaddition,an
updatedpanelcongurationmaybesenttothepanelthroughthetelephone
lines.Thepanelhaslineinandlineouttoallowthepaneltobeinstalled
aheadofothertelephoneequipmentonthepremises.
Thepanelwillsupportuptofour(4)oftheRA-6075remoteannunciators
ontheP-Linkbus.Theseannunciatorsincludeametalenclosurewitha
keylockandprovidefullfunctionalityofthesystem.
Thepanelispre-programmedfromthefactoryformonitoringatypical
wetordryresprinklersystem.Theprogrammingmaybechangedusing
thePotterFirePanelProgrammer(availablefreefromwww.pottersignal.
com)andastandardEthernetcable.Thedefaultprogramisasfollows:
Input1-Waterow
Input2-SmokeDetection(two-wire)
Input3-ManualPullStation
Input4-Non-LatchingSupervisory
Input5-ValveTamper
Input6-ValveTamper
7165-0328:0204
S735
NYC Fire Dept.
Certicateof
Approval
6282
Size(HxWxD) 18-1/2"x14-1/4"x4-3/4"
Enclosure
Eighteen (18) gauge sheet steel with hinged,
removablelockeddoor
AC Mains 1.0amp@120VAC60Hz
Battery
105mAStandby
160 mA Alarm
Temperature 32°to120°F,humidity93%non-condensing
Standards/
Approvals
UL-864
NFPA-70,72
Technical Specications