SECTION 5 POTTERTON COMMERCIAL PRODUCTS DIVISION
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
PAGE 20
PARAMOUNT
Display on room control module RRG
Progra
m
No.
BUM parameter final user
level
Function Basic Setting
(set at factory)
New
Setting *)
546
547
551
552
553
555
556
557
558
561
562
563
584
596
598
ZbreMinL
ZregiVerz
Kon
HydrSystem
KonfigHks
KonfigRg1
KonfigRg2
KonfigRg3
KonfigRg4
KonfigRg7
pH2Omin
PHOmax
ZkickFkt
ZeitAuZu
LmodRgVerz
Minimum running time for burner.
Control delay after burner start-up.
Constant for rapid reduction (without room influence)
Hydraulic system setting
Assignment of HKM or RRG to heating circuit (0…255), see
Table 11.
Adjustment codes
Adjustment codes
Adjustment codes
Adjustment codes
Adjustment codes
Min. boiler water pressure
Max. boiler water pressure
Time for pump output kick function
Running time for drive in heating circuit 2(CIM);30 to 873s
Output during control delay time
0 s
60 s
2)
4
2
21
00110100
00000000 (not used)
00000100 (not used
01000000
00001110
0.7bar (not activated)
2.5bar (not activated)
5 s
2)
150 s
25%
2)
604
605
606
607
614
615
618
619
620
621
622
623
LPBKonfigO
LPBAdrGerNr
LPBAdrSegNr
TbwBereit
KonfigEingang
KongigAusgang
KonfigEingangR
KonfigAusgang 1R
KonfigAusgang2R
KonfigAusgang3R
TanfoExtMax
PAnfoExtSchwelle
Adjustment code for bus module CIB
LPB application address for BMU
LPB segment address for BMU
Reduced setting for hot water
Programmable input F2
0 = Standard; 1 = Modem function
2 = Modern function “neg. logic”; 3 = Door veil
7 = not used on PARAMOUNT
Programmable output M5
0 = Standard; 1 = Signal output; 2 = Alarm output
3 = Operating signal; 4 = External transformer
(transformer T2); 5 = M5 (Q2Y2);
6 = DHW circulation pump; 7 = Door veil
8 = Primary loop pump M1; 9 = Primary loop pump M5;
10 = Basic function K2; 11= DHW loading
function (layer tank only); 12 = Analogue threshold
13 = control of flue gas flap
Programmable input on relay module CISP
0 – 3 = not available with CISP relay module
4 = temperature setpoint; 5 = heat output setpoint;
6 = sensor hydraulic switch
7 = not used on PARAMOUNT
Function of output 1 relay module CISP
0 = Standard; 1 = Signal output; 2 = Alarm output;
3 = Operating signal; 4 = External transformer
(transformer T2); 5 = M2 (Q2Y2)
6 = DHW circulation pump; 7 = Door veil
8 = Primary loop pump; 9 = Primary loop pump M 5
10-11 = not available; 12 = Analogue threshold
13 = control of flue gas flap
Function of output 2 relay module CISP
Setting possibilities as parameter 619
Function of output 3 relay module CISP
Setting possibilities as parameter 619
Max. value of heat demand in case of external temperature
setpoint (if param. 618 = 4)
Switchpoint of the analogue threshold
(% of max. value) (if parm. 618 = 4)
00010000
1 - -
0 - -
40°C
0
2
0
2
3
4
100°C
5%
632 WanfoQ8 Heat demands to be satisfied by primary loop pump M5 (only
if param. 615 or 619 or 620 or 621= 9)
b0.0, b1.0, b2.0,
b3.0, b4.0, b5.0,
b6.0, b7.0