Protection Automatic self-test & discharge protection, Replace battery
indicator
Back - u
Time 10 - 30 minutes (depending on computer load)
Net Weight
Kg(lbs)
13.8
30.4
14.5
(31.9)
15
(33.0)
15.8
34.8
25
55.0
30
66.0
Shi
in
Wei
ht
Kg(lbs)
14.8
32.6
15.5
(34.1)
16
(35.2)
16.8
37.0
27
59.4
32
70.4
Dimension(mm)
WxDxH
140x445x200 140x445x200 170x450x215
In
ut Inlet IEC 320
ower inlet
PHYSICAL
Receptacles NEMA 5-15R
115V
/IEC 320 female a
liance cou
ler
230V
Battery
Back-U
Slow beeping sound (about 0.25Hz)
Battery Low Rapid beeping sound (about 1.00Hz)
ALARM
Overload Continue beeping sound
INTERFACE RS-232
Bi-directional communication port
Safety cUL, TUV, CE, meet FCC
Surge Meet IEEE 587 standard
CONFORMANCE
Warranty Two years
Ambient
o
eration
6,000 meters max. elevation, 0-95% humidity non-condensing
0-40 de
C
Audible noise <40dBA
1 meter from surface
<45dBA
1 meter from surface
ENVIRONMENT
Storage
condition
15000 meters max. elevation
14. Specifications
MODEL SMK SMK SMK SMK SMK SMK
800A RM 1250A RM 1500A RM 2000A RM
Capacity 800VA 1250VA 1500VA 2000VA
Volta
e +/-25% at line in
ut , Sin
le
hase
INPUT
Fre
uenc
50 or 60Hz +/-5%
auto sensin
Voltage
(on battery)
Pure sine wave output at +/-5% of nominal, -
10% after low battery
warning
Frequency
(on battery)
50 or 60Hz +/-0.5%
OUTPUT
Voltage
Regulation
AVR
AVR automaticall
increase out
ut volta
e 15% above in
ut volta
e if
-9% to-25% of nominal. AVR decrease out
ut volta
e 15% below in
ut
voltage if+9% to +25% of nominal
S
ike Protection 320 Joules, 2ms
Unit Input Fuse for overload & short circuit protection
EMI/RFI filter 10dB at 0.15MHz
50dB at 30MHz
Overload
Protection
UPS automatic shutdown if overload exceeds 110% of nominal at
20
second and 125% at 2 seconds.
Transfer Time 2/4 milliseconds, including detection time
PROTECTION
AND
FILTERING
Short Circuit UPS output cut off immediately or input fuse / breaker protection
Type Hot swappable, Sealed, Maintenance-free lead acid , with 3-6 years
lifetime
BATTERY
Typical
Rechar
e Time
4 hours (to 90% of full capacity)