P84905-001 A Sheet 30 of 36
Example 14: NON-RESETTABLE POWER APPLICATION
FACP
DEVICE OR EOLR (10K OHMS)
TO NEXT AUXILIARY
AUXILIARY
DEVICES
SUPERVISORY
NAC
EOLR COMPATIBLE
WITH FACP
10K OHMS
EOLR
DEVICE OR EOLR (10K OHMS)
TO NEXT AUXILIARY
DEVICE OR EOLR (10K OHMS)
TO NEXT AUXILIARY
DEVICE OR EOLR (10K OHMS)
TO NEXT AUXILIARY
IN1 IN2
CC1 CC2
SBUS
IN
SBUS
RET
SIL
IN
RET1
RET2
COM
NO
NC
TROUBLE
AUX
OUT
NAC1
OUT
NAC2
OUT
NAC3
OUT
NAC4
OUT
TB1
TB2
TB6
TB3
TB4
SW2
SW1
SW3
SW4
IN2 FOLLOWER OFF/ON
TROUBLE LATCH OFF/ON
SBUS IN1/IN2
GF DETECT ON/OFF
SBUS SYNC/TEMPORAL
SYNC PROTOCOL
SYNC PROTOCOL
NAC1-NAC2 CLASS A/B
NAC3-NAC4 CLASS A/B
AUX POWER CP/MP
SBUS MASTER/REMOTE
NAC4 SYNC/TEMPORAL
NAC4 IN1/IN2
NAC3 IN1/IN2
NAC2 IN1/IN2
NAC1 IN1/IN2
IN1 FOLLOWER OFF/ON
SW6
NAC3 SYNC/TEMPORAL
NAC2 SYNC/TEMPORAL
NAC1 SYNC/TEMPORAL
D30
IN2
D31
D36
INPUT1
INPUT2
D38
SILENCE
D2
GENERAL TROUBLE
D37
ACTIVE
SW5
D40
D3: GROUND FAULT TROUBLE
D4-D8: SEE
TABLE 9
< D8-D4 >
SYNC BUS
GROUND FAULT
LOCATOR
D9
POWER
D1
IN1 TROUBLE
X
The maximum current rating for a NAC OUT circuit is 3.0 Amps.
The maximum current rating for all NAC OUTS must not exceed 4.0 Amps.
For a List of Compatible Auxiliary Devices see table in Section 8.0 on sheet 33.
Note: Continuous duty power supply outputs ARE NOT battery backed up. These outputs will TURN OFF if AC
Mains power is lost. These outputs will AUTOMATICALLY TURN ON when AC Mains power is restored.