For Natural Gas Operation : Connecting to NG Source
a. LPG / Propane and Natural Gas systems must be installed and used in strict conformance with
NFPA 58 (Liquefied Petroleum Gas Code), NFPA 54 (National Fuel Gas Code), manufacturer's
recommendations, and all relevant local, state, and federal codes and regulations.
b. Natural Gas source must meet requirements listed in Specifications chart on page 3.
c. Connect to Natural Gas source using PREDATOR
®
1/2" NG Quick
Connect Hose Kit only, item 70491 (not included). Kit includes
7.6 meter (25 ft) Hose. Do not use NG Hose with any other appliances.
d. An NG shutoff valve (not included) must be installed before connecting
the NG Hose. Do not connect NG Hose directly to the NG source.
e. Position the Generator so the connection between the NG shutoff valve
and the LPG / NG Inlet will not cause sharp bends or kinks in the Hose.
f. Make sure the NG source location and the NG Hose allow the Generator
to be located at least 20 feet from any occupied spaces.
g. Inspect the NG Hose before every use. Do not use damaged equipment.
If damage is detected, have the problem corrected before further use.
WARNING! EXPLOSION HAZARD. TO PREVENT SERIOUS INJURY:
Do not start the engine if the smell of Natural Gas hangs in the air. Close the
NG shutoff valve and disconnect the NG hose from the Generator when not in use.
1. Turn the Generator OFF and place on a
flat surface in a well ventilated area.
2. Verify that the NG shutoff valve is
in the fully closed position.
3. Attach the Quick Connect Adapter on the
NG Hose to the LPG / NG Inlet on the Generator.
4. Connect the Coupling from the NG Hose
Kit to the shutoff valve, then connect the
NG Hose assembly to Coupling.
Note: Natural gas pipe sealant, joint
compound, or the proper type of PTFE tape
must be used ONLY for the connection
from the Coupling to the shutoff valve.
5. Turn the NG shutoff valve to the fully open position.
Check for leaks by applying soapy water to all
connections and joints. Look for bubbles. If bubbles
are present at connections, close the shutoff
valve and tighten connections. Open the valve
and recheck connections. If a leak continues or
is not at a connection do not use the Generator.
Have the problem corrected before further use.
Remote Start
The Start / Stop Remote Control will operate up
to approximately 100 feet in distance from the
Generator. The distance at which the Remote will
function may be adversely affected by obstructions
between the Generator and the Remote Control.
Note: The operational range of the Remote Control may
decrease as the battery in the Remote become depleted.
Remote replacement battery: CR2032
LPG / NG Inlet
NG Hose
NG
Shutoff
Valve
Close NG
Shutoff Valve
Open NG
Shutoff Valve