CONTROL FUNCTIONS
Protective functions
– Compressors stops when:
– High pressure exceeds 108 bar.
– Restarts with manual reset.
– Low pressure is below 15 bar.
– Automatic reset.
–
BLDC Power + Alarm. See display information. Compressor
auto reset.
– 5 times before alarm becomes manual.
– Compressor out of envelope alarm. Compressor auto reset.
– 5 times before alarm becomes manual.
– EC Gas cooler fan is protected by internal temperature sensor.
– Automatic reset.
– All alarms are visible after pressing the flashing red warning triangle.
Hold down to reset. Example here: suction
pressure
probe broken
or
disconn
ec
t
ed.
Alarm
li
st
A complete list of controller alarms can be found on appendix 2.
31