CONTROL FUNCTIONS
Protective functions
Compressors stops when:
High pressure exceeds 108 bar.
Restarts with manual reset.
Low pressure is below 15 bar.
Automatic reset.
BLDC Power + Alarm. See display information. Compressor
auto reset.
5 times before alarm becomes manual.
Compressor out of envelope alarm. Compressor auto reset.
5 times before alarm becomes manual.
EC Gas cooler fan is protected by internal temperature sensor.
Automatic reset.
All alarms are visible after pressing the flashing red warning triangle.
Hold down to reset. Example here: suction
pressure
probe broken
or
disconn
ec
t
ed.
Alarm
li
st
A complete list of controller alarms can be found on appendix 2.