P.1
P.1
3505 HUTCHINSON ROAD
CUMMING, GA 30040-5860
Digital Pressure Switch /
Transmitter
Compact combination Pressure Switch / Transmitter with 2 digital outputs (NPN or PNP)
which may be set individually and an analog 4-20mA output. Perfect for the factory floor
or installed in a control cabinet. The unit comes with a 2 meter cable for easy installation
and has 2 optional mounting brackets available.
Models:
QPSL-AP-42
QPSL-AN-42
QPSH-AP-42
QPSH-AN-42
Box Contents and Unpacking Instructions
• Unpack the QPS Pressure Switch from its
shipping carton. Included in the carton is the
switch, cable and pressure units label and these
instructions.
• Inspect all equipment for completeness. If any-
thing is missing or damaged, immediately call
the AutomationDirect returns department @
1-800-633-0405.
• Inspect the part number to ensure the model
received matches the output type required.
WARNING: To minimize the risk of potential safety problems, you should follow all applicable local
and national codes that regulate the installation and operation of your equipment. These codes vary
from area to area and it is your responsibility to determine which codes should be followed, and to
verify that the equipment, installation, and operation are in compliance with the latest revision of
these codes.
Equipment damage or serious injury to personnel can result from the failure to follow all applicable
codes and standards. We do not guarantee the products described in this publication are suitable for
your particular application, nor do we assume any responsibility for your product design, installation,
or operation.
If you have any questions concerning the installation or operation of this equipment, or if you need
additional information, please call us at 1-800-633-0405 or 770-844-4200.
This publication is based on information that was available at the time it was printed. At
Automationdirect.com® we constantly strive to improve our products and services, so we reserve the
right to make changes to the products and/or publications at any time without notice and without
obligation. This publication may also discuss features that may not be available in certain revisions of
the product.
WARNING! Electric shock danger
ProSense QPS is a pressure measurement device. DO NOT use it out of its specification. Improper
pressure or incorrect wiring may cause injuries to staff or damages to other devices.
1. Keep away from high-voltage and high-frequency environment during the installation to prevent
interference. Avoid using the device in environments which contain: (a) dust or corrosive gas; (b)
high humidity and high radiation; (c) shock and vibration
2. QPS can only be used for air pressure measurement and should avoid corrosive, inflammable or
toxic gas measurement.
3. Make sure the input power is switched off when installing or uninstalling the QPS and the pres-
sure source is off to prevent harm to personnel or equipment.
4. Before switching on the input power, check the signal connection, e.g. the input voltage and
polarity. Voltage that is too high may cause damage to the QPS.
5. Use dry cloth and DO NOT use acid or alkaline liquid to clean the device.
6. Outputs remain active in Setup Mode.
x
QPSL-AN-42
QPSH-AN-42
QPSL-AP-42
QPSH-AP-42
QPS-CBL (Included with each QPS switch/transmitter)
1 - Positive input power (brown)
2 - Digital output 1 signal (black)
3 - Digital output 2 signal (white)
4 - Analog output signal (orange)
5 - Negative power supply input (blue)
12
3
4
5
2
OUT
1
OUT
ANALOG
NPN
(4-20mA output)
Input Power
10.8 to 26.4VDC
ProSense QPS Digital Pressure Switch / Transmitter Specifications
Model
QPSL-AP-42 QPSL-AN-42 QPSH-AP-42 QPSH-AN-42
Rated Pressure
-14.5 to +14.5 psi -14.5 to +145 psi
Maximum Pressure (Proof)
29psi 217psi
Maximum Vacuum
-14.5 psi
Pressure Accuracy
w 3% of full scale
Temperature Influence @ 25°C
w 2% of full scale
Fluid Measured
Air, Non-corrosive gas, Non-flammable gas
Input Power
10.8 to 26.4 VDC
Power Consumption
260mA maximum
Digital
Outputs
Output Type
2-PNP 2-NPN 2-PNP 2-NPN
Maximum Current
100mA each
Response Time
2ms, 4ms, 10ms, 30ms, 50ms, 100ms, 250ms, 500ms, 1,000ms, 5,000ms
selectable
Residual Voltage
1.5 VDC
Analog
Output
Output Type
4-20mA
Maximum Output
Load Resistance
400ΩΩ
Linear Accuracy
< w 2% of full scale
Process Connection
1/8” NPT outer / M5 inner bore (Nickel Plated Brass)
Case Materials
Case = ABS Plastic, Lens = Polycarbonate
Shock Immunity
10 ~ 500 Hz, 10mm 3 axes for 2 hours
Vibration Immunity
Max. 100m / s2 3 axes 6 directions, 3 times each
Operating Temperature
0°C to +50°C (32°F to 122°F)
Storage Temperature
-20°C to +65°C (-4°F to 149°F)
Altitude
< 2,000m
Ambient Humidity
35% ~ 80% (non-condensing)
Approvals
cULus - UL 508 (E157382), CE, RoHS