UZK24.262/-E1, UZO24.262/-E1
BATTERY MODULE 24V, 26AH, 40A
Apr. 2022 / Rev. 0.3 DS-UZK/UZO24.262-xx-EN
All parameters are typical values specified at 25°C ambient temperature unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4. INSTRUCTIONS FOR REPLACING BATTERIES
Batteries need to be replaced periodically. The time interval depends on the ambient temperature in which the battery is used and on
the number and depth of discharge cycles. In a typical application it is recommended to replace the batteries at least every 2 years.
Disconnect battery fuse before replacing the battery.
Regarding disposal of used batteries see chapter 5.
Fig. 4-1 Replacing the battery
To replace battery:
ATTENTION! Disconnect battery fuse before replacing the battery.
1) Loosen screw of battery holder with only one turn.
Remove Insulating caps from the battery terminals.
2) Unscrew the battery terminals.
3) Slide the mounting bracket sideways and take the mounting
bracket off.
4) Remove the battery.
5) Insert the new battery.
6) Fix it again with the mounting bracket and make sure that
the lock washer lies between the screw head and mounting
bracket.
7) Screw the mounting bracket with tightening torque: 2Nm (18
lb.inch).
8) Do not over-tighten screws of the terminal bolts of the
battery. Recommended tightening torque: 2.5Nm (22
lb.inch)
9) Insert battery fuse
5. INSTRUCTIONS FOR DISPOSAL OF THE BATTERIES
Batteries must be completely discharged before replacement and can be returned to the supplier of the battery module or the battery
manufacturer for disposal.
Always dispose batteries through a recycling organization.