UZK24.262/-E1, UZO24.262/-E1
BATTERY MODULE 24V, 26AH, 40A
Apr. 2022 / Rev. 0.3 DS-UZK/UZO24.262-xx-EN
All parameters are typical values specified at 25°C ambient temperature unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
The battery module includes a monitoring and
protection board. This board contains a
temperature sensor and a center-tap connection
with an auto-resettable fuse to protect the center-
tap wire between the battery module and the DC-
UPS control unit.
The sensor board enables to monitor and charge
the two batteries individually and precisely,
extending the service life of the batteries and
making matching of replacement batteries
unnecessary.
Usage of the sensor board is optional, the DC-UPS
will also function without the sensor board
installed.
The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring.
Centre tap and signal terminals
Maximal wire size, solid wire
Maximal wire size, stranded wire
5.2mm (including ferrules)
1.5mm (including ferrules)
3.5mm or 5mm slotted or
crosshead No 2
Recommended tightening torque
UZK24.262 / UZO24.262
UZK24.262-E1 / UZO24.262-E1
Instructions:
a) Follow national installation codes and installation regulations!
b) Ensure that all strands of a stranded wire enter the terminal connection!
c) Unused terminal compartments should be securely tightened.
d) Ferrules are allowed.
e) Do not use individual wires smaller than 6mm² (AWG 10) or longer than 2m (7ft) to avoid voltage drops on this connection