20
E07 H2O Level-Bad Tri-Probe
Tri-Probe application only. Check connections to the Tri-Probe Assembly.
Terminal J2-4 = Short Probe (Gray Wire)
Terminal J2-5 = Medium Probe (Violet Wire)
Terminal J2-6 = Long Probe (Blue Wire)
Terminal J2-7 = Tank Ground (Green Wire)
Note: To check operation, temporarily install three (3) jumpers across
terminals J2-4, J2-5, J2-6, and J2-7. This should clear Error Code E07.
WARNING: This procedure defeats the low water safety circuit. Ensure there is
an adequate amount of water in the humidifier tank before proceeding. If this
procedure clears the error code, check the Tri-Probe Assembly and its associated
wiring. Verify tank grounding to terminal J2-7. Refer to specifications page for
wiring limitations.
E07 H2O Level-Refill Fault
Tri-Probe application only. Check connections to the Tri-Probe Assembly.
Terminal J2-4 = Short Probe (Gray Wire)
Terminal J2-5 = Medium Probe (Violet Wire)
Terminal J2-6 = Long Probe (Blue Wire)
Terminal J2-7 = Tank Ground (Green Wire)
Occurs when fill valve has been on continuously for 1 hour
Check water source supply. Verify that water is actually filling the tank to
the TOP water level probe.
Note: To reset this alarm message, momentarily switch the power off and
on to the INTAC
®
Controller.
E07 H2O Level-Drain Fault
Unit did not drain properly during drain cycle. Check for sediment blockage
in drain valve and drain line. The drain duration may not be set long enough. The
water level must read “Low” during the auto drain or this fault will occur.
E08 Module I/O Error - DLCM #1
It is likely the controller has been damaged and needs replacement
E08 Module I/O Error - DLCM #2
It is likely the controller has been damaged and needs replacement
E08 Module I/O Error - WLCM
It is likely the controller has been damaged and needs replacement
A01 RH Alarm-Low RH
The actual RH is below the limit set in Configuration Menu 103
A01 RH Alarm-High RH
The actual RH is above the limit set in Configuration Menu 104