5.6 Suitable breaker
1) The rated voltage shall ≥60V DC. Do NOT use AC breaker.
2) The type of breaker shall be type C (recommended) or type D.
3) The rated current shall match with system design:
shall consider the DC current on inverter side.
the number of power cable: for instance, if only one pair of 4awg cable, the
rated current of breaker shall be 125A or smaller.
4) The Icu required:
the short circuit current for calculation of each module is 2500A. for instance:
Icu of breaker
1~4 modules
Must ≥10kA
5~8 modules
Must ≥20kA
5.7 Power on
Double check all the power cable and communication cable.
1) Switch on all the battery modules:
2) The one with empty Link Port 0 is the Master Battery Module, others are
slaves (1 master battery configure with maximum 15 slave batteries):