POS. +24/48 VDC
NEG. -24/48 VDC
OPTI ONAL D C
POWER INPUT
Ground
RH+
RH-
T+
T-
NC
ZONE 1
TEMP AND HUMIDITY
ZONE 2 TEMP
OUTDOOR
AIR SENSOR
HVAC LO CKOUT
HIGH TEMP L2
SMOKE ALARM
HIGH TEMP L1
CONTROL VOLTAGE LOSS
LO W TEMP
GENERATOR RUNNING
TOXIC GAS
SMOKE ALARM
A/C #2
BARD H**4 HVAC SYSTEMS
ALARM SHOWN WIRED NORMALLY CLOSED
3
2
9
7
4
6
14
5
COMMON
24VAC
FAN
COOL 1 ECON
MECH COOL
CLOSE DAMPER
HEAT
EMERG. VENT
2
1
16
17
AC LOCKOUT
2
1
JUMPER TERMINAL 4 TO 5 TO CLOSE DAMPER WHEN IN MECHANICAL COOLING. THIS A SSUMES JADE CONTROLLER IS
CONFIGURED TO CLOSE DAMPER WITH AUX2 INPUT. JUMPER CAN BE LEFT OFF IF IT IS ACCEPTABLE TO HAVE
DAMPERS OPEN WHEN IN MECHANICAL COOLING
NOTES:
1. SET JADE CONTROLLER TO ECONOMIZE AT 74 DEGRE E OSA
2. CONFIGURE SETUP FOR SINGLE STAGE INT EGRATED OR QUEST MODE ECONOMIZER.
3. OSA SENSOR MUST BE CONNECTED FOR QUEST MODE
ASSUMES JADE CONTROLLER IS CONFIGURED FOR 100% OSA WHEN THE OCCUPIED INPUT IS ACTIVE
3
2
9
7
4
6
14
5
COMMON
24VAC
FAN
COOL 1 ECON
MECH COOL
CLOSE DAMPER
HEAT
EMERG. VENT
2
1
16
17
AC LOCKOUT
A/C #1