Rev 3.1 01/11/23 - 15 - Model 600 User Guide
3.5.2 Setpoint Menu
The setpoint value used for mechanical cooling
The setpoint value used when econ mode is enabled.
The number of degrees subtracted from the cool and
econ setpoint when in comfort mode.
The number of degrees below the cooling SPT (or econ
spt if enabled) before turning off cooling.
The setpoint value used for heating
The number of degrees added to the heat setpoint
when in comfort mode.
The number of degrees the control temperature is
above the heating setpoint to turn off heating.
When the %RH is above this setting, the system will go
into dehumidification mode and use the dehumid
setpoints for cooling and heating. A value of 0 disables
this function.
When using RH dehumid control the humidity sensor
has to be below the RH Control SPT minus this value to
disable Dehumid control mode
The cooling setpoint to use when in Dehumid mode.
The heating setpoint to use when in Dehumid mode.
The number of degrees above the cool SPT to enter
cool 2 mode.
The number of degrees above the cool SPT plus stage 2
delta to enter cool 3 mode.
The number of degrees above the cool SPT plus stage 2
and stage 3 deltas to enter cool 4 mode.
The number of degrees below the heat setpoint to
enter heat 2 mode.
The number of hours before switching the lead system.
0 = disable and will not switch leads based on time.
The number of minutes for comfort mode to be active
when the button is pressed. 0 disables comfort mode
function
The number of seconds that a cooling or heating stage
must be on before it can be turned off to prevent short
cycling.
The number of seconds to wait once a stage or cooling
or heating is off before it can come back on.