Rev 3.1 01/11/23 - 15 - Model 600 User Guide
3.5.2 Setpoint Menu
Setpoint Option
Available Choices
Description
Cool SPT
60-110 (80)
The setpoint value used for mechanical cooling
Econ SPT
60-110 (75)
The setpoint value used when econ mode is enabled.
CMFT Cool Delta
1-20 (5)
The number of degrees subtracted from the cool and
econ setpoint when in comfort mode.
Cool Off Delta
1-20 (2)
The number of degrees below the cooling SPT (or econ
spt if enabled) before turning off cooling.
Heat SPT
30-70 (55)
The setpoint value used for heating
CMFT Heat Delta
1-20 (10)
The number of degrees added to the heat setpoint
when in comfort mode.
Heat Off Delta
1-20 (2)
The number of degrees the control temperature is
above the heating setpoint to turn off heating.
RH Control SPT
20-100 (0)
When the %RH is above this setting, the system will go
into dehumidification mode and use the dehumid
setpoints for cooling and heating. A value of 0 disables
this function.
RH Ctrl Off Delta
2-50 (20)
When using RH dehumid control the humidity sensor
has to be below the RH Control SPT minus this value to
disable Dehumid control mode
Dehumid Cool SPT
60-110 (65)
The cooling setpoint to use when in Dehumid mode.
Dehumid Heat SPT
30-70 (65)
The heating setpoint to use when in Dehumid mode.
Cool Stg 2 Delta
1-20 (2)
The number of degrees above the cool SPT to enter
cool 2 mode.
Cool Stg 3 Delta
1-20 (2)
The number of degrees above the cool SPT plus stage 2
delta to enter cool 3 mode.
Cool Stg 4 Delta
1-20 (2)
The number of degrees above the cool SPT plus stage 2
and stage 3 deltas to enter cool 4 mode.
Heat Stg 2 Delta
1-20 (2)
The number of degrees below the heat setpoint to
enter heat 2 mode.
Lead Swtch Hours
0-336 (168)
The number of hours before switching the lead system.
0 = disable and will not switch leads based on time.
Comfort Minutes
0-240 (60)
The number of minutes for comfort mode to be active
when the button is pressed. 0 disables comfort mode
function
Stg Min On Time
30-600 (120)
The number of seconds that a cooling or heating stage
must be on before it can be turned off to prevent short
cycling.
Stg Min Off Time
30-600 (120)
The number of seconds to wait once a stage or cooling
or heating is off before it can come back on.