D9000/D7000 Series Installation and Troubleshooting Quick Reference
Page 2
33317D 4/97
Basic Troubleshooting
Service Walk Test Shows Extra Points
The Service Walk Test differs from the standard Walk Test in that POPITs whose switches
are set for a point number not programmed in the panel appear in the test.
Service Walk Test only available at Command Centers with panel wide scope:
See
Command Center
in the
D9000/D7000 Series Control/Communicator Program Entry Guide
(74-07695-000) for a description of Command Center scope.
Warning, fire and other 24-hour points do not transmit reports during Service Walk
Test!
The steps below outline a simple Service Walk Test procedure. The flow chart on the next
page shows all the Service Walk Test options.
1. Choose a Command Center with panel wide scope to conduct the test. Be certain the
display shows the idle disarmed text.
2. Enter a valid service passcode and press the ENT key to enter the Function List.
Press NEXT repeatedly until you reach the
SERVICE WALK ?
prompt. Press ENT.
3. The display shows
### PTS TO TEST
. Test the first detection device.
4. As you fault the detection devices, the Command Center emits a brief tone and
displays the point text of the point tested for 60 seconds. After 60 seconds, the display
returns to the points to test message.
Extra Points display default text:
If you incorrectly set the switches on a POPIT to a
point number that is not in your program for the panel, the default text for that point
number (
PT ###
) displays when you fault the point. The Program Record Sheet
shows
the default text for all points.
Faulting the point a second time produces the tone and displays the point text, but
does not reduce the
PTS TO TEST
count.
5. During the Service Walk Test you may want to see the points that remain untested.
When point text is displayed, press CLEAR. The display shows
## PTS TO TEST
.
Press the CLEAR key.
VIEW UNTESTED ?
is displayed. Press ENT.
## PTS
UNTESTED
is displayed. Press NEXT to see a list of the points that have not yet been
tested. Move through this list by pressing the NEXT key. To resume the Service Walk
Test, press CLEAR.
## PTS UNTESTED
is displayed. Press CLEAR.
## PTS TO
TEST
is displayed. Resume testing points. To end the Service Walk Test, press
CLEAR twice.
6. After testing the last point,
0 PTS TO TEST
displays. Press CLEAR. The display
momentarily shows
ALL PTS TESTED
before returning to idle text.
Automatic time-out returns the system to idle text:
If there is no point or Command
Center activity for 20 minutes, the walk test ends automatically. The Command Center
returns to idle text.

Other manuals for Radionics D7412

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Radionics D7412 and is the answer not in the manual?

Radionics D7412 Specifications

General IconGeneral
BrandRadionics
ModelD7412
CategoryControl Systems
LanguageEnglish

Related product manuals