DESCRIPTION/APPLICATION
RANCO commercial pressure controls are used for either
operating or protecting commercial refrigeration or air
conditioning systems. They are suitable for R12, R22, and R502
refrigerants and are available with either male are or capillary are
nut connections. Both low pressure (suction sensing) and high
pressure (discharge sensing) versions are available.
These controls, with NEMA 1 enclosures and snap action switches,
may be used in a variety of applications: direct control of motors
or compressors; with a contactor for pilot duty control; to control
solenoid valves. The electrical ratings inside the control cover must
not be exceeded.
O10 Single pole, single throw (SPST)
close (cut-in) on rise
open (cut-out) on drop
O11 Single pole, single throw (SPST)
open (cut-out) on rise
close (cut-in) on drop
O16 Single pole, double throw (SPDT)
2-3 close on rise, open on drop
2-1 close on drop, open on rise
O20 Double pole, single throw (DPST)
close (cut-in) on rise
open (cut-out) on drop
3
2
1
L
L T
T
DIFFERENTIAL
ADJUSTMENT
SCREW
CW increases
CCW decreases
See p. 3
RANGE
ADJUSTMENT
SCREW
CW lowers
CCW raises
See p. 3
COVER
SCREW
All O series are available in the automatic reset/cycling version.
Manual reset versions of the O16 are available.
NO! NO!
DIFF HIGH EVENT
3
12”
0
10
20
30
40
50
0
1
2
3
35
25
15
5
2
1
PSI. bar
CLOSES ON PRESSURE RISE.
SWITCH LOW EVENT
IS HIGH EVENT
MINUS DIFF
bar PSI.
DIFF HIGH EVENT
3
12”
0
10
20
30
40
50
0
1
2
3
35
25
15
5
2
1
PSI. bar
CLOSES ON PRESSURE RISE.
SWITCH LOW EVENT
IS HIGH EVENT
MINUS DIFF
bar PSI.
DIFF HIGH EVENT
3
12”
0
10
20
30
40
50
0
1
2
3
35
25
15
5
2
1
PSI. bar
CLOSES ON PRESSURE RISE.
SWITCH LOW EVENT
IS HIGH EVENT
MINUS DIFF
bar PSI.
YES!
IMPORTANT NOTICE
MANUAL OPERATION (tripping switch)
The switch can be manually operated by lifting
the bellows to tabs as shown. Operating the
control at any other point WILL CAUSE
CONTROL DAMAGE AND VOID THE
WARRANTY.
DO NOT REMOVE the protective switch cover.
INSTALLATION
CAUTION:
To prevent possible electrical shock or equipment damage,
disconnect electrical power to unit before and during installation.
DO NOT restore electrical power to unit until the control is properly
installed and grounded. DO NOT locate the control in an explosive
atmosphere as a safety hazard can result due to possible spark
generation in the control.
Controls are not to be located in areas of extreme moisture,
dirt or dust, or in a corrosive or explosive atmosphere. These envi-
ronments can shorten control life.
1
INSTALLATION DATA
O10/011/O16/O20
SINGLE PRESSURE CONTROL
Question and Answer IconNeed help?

Do you have a question about the Ranco O10 and is the answer not in the manual?

Ranco O10 Specifications

General IconGeneral
MountingPanel
TypeTemperature
Input Voltage120/240V AC
Sensor TypeLiquid Filled
TerminalsScrew
S.P.D.T.Single pole, double throw

Summary

Description and Application

Installation and Safety

Installation Caution

Critical safety warnings regarding electrical power, grounding, and explosive atmospheres.

Manual Operation Instructions

Instructions for manual operation of the control switch, with warnings.

Control Body Mounting Methods

Compressor Mounting

Guidelines for mounting the control directly onto the compressor unit.

Remote Mounting

Procedures for mounting the control away from the compressor with vibration isolation.

Capillary Care and Mounting

Control Wiring and Settings

Control Wiring

Guidelines and precautions for wiring the pressure control.

Low Pressure Control Settings

Guidelines for setting low-pressure controls and minimum vacuum limits.

High Pressure Control Settings

Guidelines for setting high-pressure controls and maximum pressure limits.

Adjustment Examples and Checks

Close on Rise Control Adjustment

Examples of adjusting cut-in and differential for close-on-rise controls.

Open on Rise Control Adjustment

Examples of adjusting cut-out and differential for open-on-rise controls.

Low Pressure Control Check

Procedures for checking and verifying low-pressure control settings.

High Pressure Control Check

Procedures for checking and verifying high-pressure control settings.