TRACETEK
DESCRIPTION
The nVent RAYCHEM TraceTek TTC-1 sensing module is used with
TraceTek sensing cables to detect liquid leaks. The module provides
visual indication when a leak or cable break has occurred and has
relay contacts to connect the TTC-1 to external devices for remote
monitoring and control.
ELECTRICAL CODES
Installation must be done in accordance with national and local
codes and regulations that apply. The TTC-1 must be installed in
ordinary areas only.
MODULE LOCATION
Enclosure rating: IP 20 / NEMA 1
Operating temperature range: 0ºC to 50ºC (32ºF to 122ºF)
SPECIFICATIONS
Maximum sensing cable length: 250 ft (76 m)
Leader cable length is not included in the length limitation.
Input power:
12 to 24 Volts AC – 0.25 A
15 to 24 Volts DC – 0.15 A
When using a transformer, use UL listed Class II transformer
rated at 24 V, 20 VA
Recommended fuse rating: 3 A
Relay ratings: 3 A: 30 Volts DC or 24 Volts AC
INSTALLATION MATERIALS AND TOOLS REQUIRED
Wall fastener (2 ea for surface mounting only)
PARTS AND MATERIALS
1 ea TTC-1 Sensing Module
1 ea TTC-1 Wall Label
4 ea Strain Reliefs
OPTIONAL ACCESSORIES
TTC-DRC DIN Rail Clip – Part # 062825-000
TTE-XAL External Loud Alarm – Part # 418569-000
TT-MAP-TOOL – Part # E43135-000
APPROVALS
General Signaling Equipment
76LJ
TYPE NM
Figure 1: TTC-1 Module
4.2 in
(106 mm)
2 in
(52 mm)
4.4 in
(112 mm)
TRACETEK
IMPORTANT NOTES
The TTC-1 module is designed for use with TraceTek sensing
cables and probes only. A TTC-1 based system will detect and
alarm on all fluid leaks detected by the TraceTek cable as per
the appropriate cable data sheet.
Transient spills and contamination may also activate the
system. Users should consider this operational function when
determining the suitability of the TraceTek system for specific
applications.
The system has not been designed for repetitive cycling.
Always connect the Leak Detection relay to an annunciation
device (for example the nVent RAYCHEM TraceTek TTE-XAL
External Loud Alarm) so that an operator is notified and can
verify proper operation if automatic equipment is connected.
Maintenance personnel should examine the sensing cable for
cleanliness and verify proper operation of the TTC-1 module at
least every six (6) months.
TTC-1
TraceTek Sensing Module Installation, Operation
and Maintenance Instructions
Question and Answer IconNeed help?

Do you have a question about the Raychem TRACETEK TTC-1 and is the answer not in the manual?

Summary

Product Specifications

Installing the TTC-1 Module

Terminal Block Wiring

Guide for connecting sensor, power, and relay wires to the terminal block.

Power Supply Connections

Relay Connections and Configuration

Final Reassembly

Final Installation Checklist

Operating Instructions

System Operation Overview

How the TTC-1 module and sensor cable monitor for leaks and breaks.

Leak Detection Indication

Details the indicators and relays when a leak is detected.

Power Failure Indication

Details the indicators and relays during a power failure.

Field Adjustments and Maintenance

Test Procedure

Steps for simulating leaks and cable breaks to test functionality.

Troubleshooting Guide

Leak Alarm Without Detected Leak

Addresses issues where a leak alarm occurs but no leak is found.

Cable Break Indication

Troubleshooting when a cable break is indicated but the cable appears intact.