EasyManua.ls Logo

Raypak 241275 - Troubleshooting

Raypak 241275
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
NOTE: Elodrive actuator is Nema 4 rated.
TROUBLESHOOTING
Check your power source using a Volt-Ohm meter;
check the following voltages at TB1 terminal block:
TB1-1 to TB1-2 = 108 VAC Minimum, 132 VAC
Maximum
TB1-1 to TB1-3 = 108 VAC Minimum, 132 VAC
Maximum
TB1-2 to TB1-3 = Must be less than .6 VAC
IF CALL FOR HEAT LED does not illuminate when the
heater has a CFH signal, check for 24VAC at the
heater CPW Board (J17-TRIG) output. If voltage is
present, check wiring using the wiring diagram. If volt-
age is not present, the problem exists in the heater.
IF VALVE DOES NOT MOVE: Check for voltage out at
TB2-1: Should be a 1VDC to 10VDC output to the
actuator valve. If no voltage is present, check for volt-
age at TB2-3, there should be a 12VDC signal. If the
12VDC signal is not present, verify that the converter
is wired correctly using the wiring diagram.
IF SENSOR OUT OF RANGE LED is illuminated: The
set point temperature has not been reached within the
7 minute time period.
Push the Reset Switch (see Fig. 4) or remove
power and watch for proper operation.
Check pump sizing and valve/piping sizing and cor-
rect as necessary.
Replace sensor.
Check wiring using wiring diagram.
Fig. 8: Elodrive Actuator — Rotation Knob Setting
Fig. 9: Elodrive Actuator — Actuator Shown in Full
System Flow Position

Related product manuals