Raypak 3450 - Multiple Pool Heater Piping Configurations

Raypak 3450
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
Fig. 15: Pool Piping for Heat Pump Pool Heaters, Multiple, Primary/Secondary
EXTEND 12” PAST
HEATER INLET FOR
HYDRAULIC BALANCING.
2450-4450
BRANCH MAINBRANCH MAIN BRANCH MAIN
20 GPM1-1/2"1-1/2"20 GPM 1-1/2" 1-1/2" 20 GPM1-1/2"2"
30 1-1/2" 1-1/2" 30 1-1/2" 2-1/2" 30 1-1/2" 3"
40 1-1/2" 2" 40 1-1/2" 3
*Sizing based on10 ft/sec flow rates
MINIMUM PIPE SIZES
2 UNITS3-4 UNITS 5-6 UNITS
5450-8450
BRANCH MAINBRANCH MAIN BRANCH MAIN
30 GPM
40
60
80
2"
2"
2"
2"
2"
3"
3"
4"
30 GPM
40
60
80
2"
2"
2"
2"
2-1/2"
3"
4"
4"
30 GPM
40
60
80
2"
2"
2"
2"
4"
4"
5"
5"
MINIMUM PIPE SIZES
2 UNITS3-4 UNITS 5-6 UNITS
40 1-1/2" 4"