EasyManua.ls Logo

Raypak Temp-Tracker - Page 22

Raypak Temp-Tracker
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
MODE 2
(With Default Settings Shown)
ADJUST MENU
(Page 2 of 2)
Item Field Range Description Setting
Au, 0:30 to
9:55 min
S
TAGE DELAY
Select the minimum time delay between
stages.
Note: This setting is only available when
STAGE MODE is set to PId.
Au, 2 to 42°F
(1 to 23°C)
DIFFERENTIAL
Select the boiler dierential.
Note: The automatic setting is only available
when STAGE MODE is set to PId staging.
0 to 10°F
(0 to 6°C)
STAGE DIFFERENTIAL
Select the interstage temperature dierential
between stages for proportional staging.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 8:00 min
INTERSTAGE ON DELAY
Select the amount of time that must pass
once a stage has been turned on in order
to allow the next stage to turn on.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 4:00 min
INTERSTAGE OFF DELAY
Select the amount of time that must pass
once a stage has been turned o in order
to allow the next stage to turn o.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 5:00 min
MINIMUM ON TIME
Select the minimum amount of time that
the stage contact must remain on before it
is allowed to turn o.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 5:00 min
MINIMUM OFF TIME
Select the minimum amount of time that
the stage contact must remain o before it
is allowed to turn back on.
Note: This setting is only available when
STAGE MODE is set to P.
OFF, 0:20 to
9:55 min, On
PUMP DELAY
Select the system pump purge time after
shutting o the burner.
°F or °C
TEMPERATURE UNITS
Select to display temperature in degrees
Fahrenheit or in degrees Celsius.
Table H: Adjust Menu, Mode 2 (page 2 of 2)