DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS HeatNet Control V3
Page 106
MAXIMUM RUNTIME
120 Minutes
0 - 200 Minutes
This is the maximum runtime of the boiler when DHW heating.
When this runtime is exceeded, the boiler will either Lockout or re-
cycle to the Holdoff Time setting below.
HOLDOFF TIME
30 Minutes
LOCKOUT to 120
Minutes
If set to Lockout, the boiler will no longer perform DHW Heating. A
manual reset or toggling the OR OVR input will reset the Lockout.
If a time is set, the boiler will wait this time before it can perform
DHW heating again.
PUMP ALWAYS ON
NO
ON/OFF
If set to On the domestic hot water pump rill run continuously.
TIME
This time needs to be entered at first turn-on and in the event that
power has been lost for more than 3 days. The time is required for an
accurate Night setback, log entry time-stamp, and fault time stamp.
MONTH
DAY
YEAR
WEEKDAY