DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS HeatNet Control V3
Page 106
This is the maximum runtime of the boiler when DHW heating.
When this runtime is exceeded, the boiler will either Lockout or re-
cycle to the Holdoff Time setting below.
If set to Lockout, the boiler will no longer perform DHW Heating. A
manual reset or toggling the OR OVR input will reset the Lockout.
If a time is set, the boiler will wait this time before it can perform
DHW heating again.
If set to On the domestic hot water pump rill run continuously.
This time needs to be entered at first turn-on and in the event that
power has been lost for more than 3 days. The time is required for an
accurate Night setback, log entry time-stamp, and fault time stamp.