DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS HeatNet Control V3
Page 107
CONTROL SETTINGS MENU— PAGE 2
Displays method of operation: HeatNet (H-Net)
Auto detected, based on the HEADER sensor.
If the HEADER sensor is present and is set to TYPEZ, the FlexCore
CK-Series control is run as a H-Net MASTER (YES).
If the HEADER sensor is not TYPEZ, H-Net MASTER = NO.
AUTO, MIXED
(COMBINATION),
DHW ONLY
Two PID controls are provided, one for Space heating and one for
DHW heating. This menu item selects how they are to be used. The
MASTER TYPE setting is used to determine if the MASTER
control is to be used as a space heating control, a combination
DHW/space heating control, or just to perform DHW Heating.
When set to AUTO, the boiler uses one PID control to provide space
heating. When set to Combination, the control will use two
independent PID controls to provide space heating and DHW
heating. When set to DHW, the control only uses the DHW PID
control.
The local address is the address of a member device. This is
normally in the range of 2 through 16. But if the FlexCore CK -
Series control is a MASTER, then the default address is 255.
The H-NET ADDRESS # is synonymous with boiler #.