CONTROL METHODS HeatNet Control V3
Page 41
DHW Method 3 Quick Start Settings
DHW METHOD 3: DHW Heating ONLY Using a MASTER and Member boiler(s) Employing H-Net Space Heating PID.
Master
Settings
Master Type
HeatNet Address
Combustion Air Damper
Automatic
Automatic
Off
Inputs
Local/Remote
Header Sensor
JPS1 Jumper must be cut to service DHW
Local
Yes - Tank
Outputs
Local Pump On
When Boiler Running
Member 2
Settings
HeatNet Address
Combustion Air Damper
2
Off
Inputs
Local/Remote
JPS1 Jumper must be cut to service DHW
Remote
Outputs
Local Pump/Valve On
When Boiler Running
Member 3
Settings
HeatNet Address
Combustion Air Damper
3
Off
Inputs
Local/Remote
JPS1 Jumper must be cut to service DHW
Remote
Outputs
Local Pump/Valve On
When Boiler Running