DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS HeatNet Control V3
Page 101
OVERRIDE ENABLED
IN WARM WEATHER
SHUTDOWN
Priority mode for the system pump while in Warm Weather
Shutdown. ON: The system pump is allowed to run in WWS when
the OR OVR override input is closed. When set to OFF, the system
pump will not come on while in WWS with the OR OVR override
input closed. Enabling this feature disables the SUMMER PUMP
JOG.
DELTA TEMPERATURE
ENABLED
ON: Use Delta temperature to shut pump off when temperature
across boiler is less than DELTA TEMP setting.
Time in minutes to keep local circ. pump on after boiler stops
ON: Outputs a 0-10VDC or 4-20 mA signal from J4 pins 1 & 5 that
is proportional to the fire rate of the boiler. Connect to a VFD
controlling a Local pump.
This is an adjustable flow proving time to allow slower valves to
open before proving flow.
MASTER PUMP/VALVE
REMAINS ON
ON: The Master boiler will keep its pump/valve on when no boilers
are running. Prevents deadheading the system flow.
Four setbacks (TABBED) to adjust setpoint during a time period
Enable or disable the use of this setback
Temporarily subtracts this temp from the setpoint
Day of the week to begin setback or a day range
Day of the week to end the setback or a day range
Time of the day to end the setback
Fahrenheit scale, English is default