Door control
FireProV2
Manual
Please keep this manual with attachments carefully!
21
9.12 Key switch:
On connector X11, a key switch which is placed on the lid can be connected to number 1 and 2.
This allows the control to be switched on and off. When this key switch is not used, this input
must be connected with a wire bridge to make the operation work (see Fig. 12). If the key switch is
activated, a red dot will appear at the bottom right of the display.
Key switch activated
9.13 Fire Alarm / Smoke detector:
On connector X11, the potential free NC Contact of the fire alarm or smoke detector can be
connected to number 3 and 4, which is interrupted in case of fire/calamity. If this input is not used,
it must be connected with a wire bridge (see Fig. 13). For situations with air Bellows for smoke
sealing see 9.16.
9.14 Escape button:
On connector X11, a escape button can be connected to number 5 and 6 which can be used to open
the door at fire/calamity (see Fig. 13). When inflated air bellows for smoke sealing (9.17 smoke
detection) The escape button function no longer works.
9.15 Impulse:
On connector X11, a pulse function can be connected to number 7 and 8. A control such as e.g. a
pull switch can be connected (see Fig. 13 ).
Figure 13 connecting clamp X11