29
10.9 Continuing when empty or disconnected battery:
If the door/roller shutter has passed the limit switches and the emergency switches are activated
because the batteries are empty or not connected, the door/roller shutter can be sent back up. This
can only in normal operation by pushing the open control Knob on the PCB at least 5 seconds,
after this 5 second the door/roller shutter will continue to open hold to run and can be put back in
between the end positions.
Please note!
This function does not monitor the end positions, direction of rotation and movement. Do Not
allow the door to move until halfway through the opening, in the correct direction of rotation.
10.10 Opening after passing digital limit switches
If the door/roller shutter is passed the limit switches because the batteries of the controller are
discharged too far, they can be put back in the correct position by pushing the open control Knob
on the PCB, if a motor with digital switches is applied, Press it for 5 seconds, after 5 seconds the
door/shutter will open in hold to run as long as the menu button is pressed. This allows the door to
be put back in the correct position to function normally again.
Please note!
This function does not monitor the end positions, direction of rotation and movement. Make sure
that the button is released in time.
10.11 Low battery voltage
The level at which a notification should be given that the battery has a low voltage
(< 20 volts) is adjustable by parameter 3.8 from 20 to 25 volts. A message will be displayed on the
display and the red led on the controller light up.
In the case of a voltage outage, you can chose by using parameter 3.7 to allow the door/shutter to
close in the same way as activating the BMC input.
10.12 Notifications
A potential-free changeover contact siren is present on the controller on which a siren or
warning lamp can be connected. The function of this contact can be set in Parameter 5.1.
Furthermore, there is another potential-free switch, alarm, which switches when the BMC input is
active.
There are 8 notifications that have a joint common and all are potential free N.O. contacts. These
are the following notifications:
- Limit switch Open reached
- Limit switch Close reached
- Extra limit Switch reached
- Safety chain motor interrupted
- Roll-off protection activated
- Safety edge activated/defective, adjustable with parameter 2.3 or only notification
of the safety edge or only of the photocell or both.
- Low battery voltage (limit value set at parameter 3.8 exceeded)
- No mains supply available
If the smoke detection is not used, the contact "RM close" can be made to make a notification that
an error message is active. This can be set by parameter 2.6 to 2.