9.18 Outputs:
On connector X15 (Fig. 16), 8 outputs are as potential-free N.O./contact with one common
connection. These outputs pass 8 notifications.
These are the following notifications on connection:
2. Limit switch Open reached (door/roller shutter open)
3. Limit switch Close reached (door/shutter shut)
4. Extra limit Switch reached
5. Motor safety chain interrupted (one of the emergency switches activated or the thermal
contact interrupted).
6. Roll-off protection activated
7. Safety edge activated or defect (can be changed from the menu to photocell or both
parameter 0.7)
8. Low battery voltage
9. No power supply available
Figure 16 message on connector X15
9.19 Smoke detection (only in combination with inflatable bellows):
In the case of smoke detection, the same as a fire alarm occurs. Only there are two options that can
be chosen with parameter 4.3. If the smoke message is over, a reset command must first be offered
after the door/roller shutter is cleared again.
After the reset command, the door will only active after a set time (parameter 4.5). In the
meantime, the door cannot be operated. Only then will the door/roller shutter function normally.
If the mains supply has switched off, the position of the door/roller shutter can be chosen with
parameter 4.4 (see section 10.8).
If a separate smoke detection is selected for situations with air bellows for smoke sealing , it can
be connected to X9 (Fig. 17) Connection 1 and 2 is a potential free N.C. (NC) Contact. The
Reset (parameter 4.5, 0 to 240 sec., default setting 60 sec.) for this you can connect to X9
connections 3 and 4 as potential free N.O. contact. To indicate that the door is closed when the
RMC (Smoke-detection contact) input is activated, output X14(Fig. 18) is present as a potential-
free changeover contact. If the door is equipped with Air Bellows , the compressor valve can be
controlled with this. See Figure 19 for the schedule off controlling a 24vdc valve.
When inflated air bellows for smoke sealing, the escape button function (9.13 escape button) no
longer works.
X14's potential-free contact can also be used for the test function of a light curtain if X13 contacts
have been used for the P-cap signaller.