Door control
FireProV2
Manual
Please keep this manual with attachments carefully!
11.6 Parameter settings 5. :
.1 Switches during pre-warning and when the
door/roller shutter is moving
.2 Switches only if the door/roller shutter is
moving
.3 Switches only in case of fire alarm, smoke
detection or low battery voltage during pre-
warning and if the door/roller shutter is
moving
.4 Switches only in case of fire alarm, smoke
detection or low battery voltage when the
door/roller shutter is moving
.5 Test function light curtain
Function (potential-free
N.C. contact with
common) notification
security
interrupted/defective
.1 Interrupted/defective message only for
safety edge
.2 Report only photo cell interrupted/defective
.3 Photo cell notification and safety edge
interrupted/defective
.4 Test function light curtain
.1 Switches when the door closes in case of
calamity
.2 Test function light curtain
11.7 Parameter settings 8. :
Number of cycles till
maintenance
1 t/m 99
per 1.000 cycles adjustable from 1.000 (= 1) to
99.000 (= 99)
Turn on or off
maintenance counter
Maintenance cycle
counter
Maintenance cycle counter is displayed. It
counts from the set value to 0. At zero, a
notification is given to carry out maintenance.
11.8 Parameter settings 9. :
Displays the last two error messages.
The number of changes in the menu is
displayed.
Software version is displayed
Reset to factory settings
.0 Do not reset go back to menu
.1 Run reset, restart control