Display Meaning
Cleaning Alarm
Valve current
No pressure
No drop in pressure
Filter valv.no. ###
Ctrl.## Valv.no. ###
Row 1
Row 2
Row 2
Row 2
Row 3
Row 4
Cleaning Alarm
No valve current present or
cleaning pressure too low or
no pressure drop after a cleaning pulse
on the valve with the filter number ###
Location: I/O module RM-V6/X / RM-V8 / RM-V16 with the
control number/address ## and the control valve No. ###
(valve connection faulty or valve defective).
RM-VXX comm.alarm
RM-VXX No. ##
No reply
Row 1
Row 2
Row 3
Row 4
RM-V6/X / RM-V8 / RM-V16 Communication alarm
Empty row
I/O module RM-V6/X / RM-V8 / RM-V16 with the address #
sends no response
RM-VXX alarm setting
RM-VXX
Valve setting
incorrect
Row 1
Row 2
Row 3
Row 4
RM-V6/X / RM-V8 / RM-V16 Setting alarm
The valve setting of the I/O modules RM-V6/X / RM-V8 / RM-
V16 does not agree with the setting of the RM-310 C /
RM-310 CT.
Sensor alarm #
DP-Sens.defect or
Check P-connection
Row 1
Row 2
Row 3
Row 4
Sensor Alarm #
Δp-Sensor # defective or
Δp-Connections faulty (check!)
Input Ix alarm
I < #,# mA or
not connected
Row 1
Row 2
Row 3
Row 4
Input current monitoring
Input current Ix < #,# mA
x = input 1, 2 or 3
#,# = 1.00 or 3.50 mA