Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 23 14.07.2020
5.9 Parameter list
Parameter
Code
Text in display, line 1 Meaning
Factory
setting
Setting range
See p
age
B0
B0 Disp.language
Language of the display text
0
0 … 2
25
Parameter block C0-C3 "Service operating hours counter"
C0
5
C0 Ser.ope.hours
Service operating hours counter
0
1
0
1
… 2
25
C1
C1 Counter mode
Operating hours counter mode
3
0 … 3
25
C2
4
C2 Service alarm
Service alarm
3000 h
0
1
… 25.500 h
25
C3
4
C3 Serv.al.reset
Service alarm reset
25
Parameter block D0-D8 “Δp-controls“
D0
3
D0 DP-controls
Δp controls
1
0
1
, 1
26
D1
D1 Cleaning mode
Δp cleaning mode
2
0 … 4
26
D2
D2 Sensor source
Sensor source
2
0 … 3
26
D3
D3 Sensor alarm
Sensor alarm
0
0 … 1
26
D4
D4 DP-unit
Δp unit in display
Pa
Pa, mbar, hPa,
inch/Wc
27
D5
D5 DP-start
Δp start
1000 Pa
2
100 … 4800 Pa
3
27
D6
D6 DP-hyster.
Δp hysteresis
300 Pa
4
100 … 4700 Pa
5
27
D7
D7 DP-min alarm
Δp min. alarm
0
1
Pa
0
1
… 4600 Pa
6
27
D8
D8 DP-max alarm
Δp max. alarm
2000 Pa
7
0
1
… 5000 Pa
8
27
D9
D9 DP pre-alarm
Δp-pre-Alarm max.
0
1
Pa
0
1
… 5000 Pa
8
27
1
0 = Function inactive
2
The value 1000 Pa applies to the default setting of parameter T1 = 05000 Pa. If another Δp range is selected, the Δp starting
value is 20% of the full scale value.
3
The setting range 100 Pa … 4800 Pa applies to the default setting of parameter T1 = 0 5000 Pa. If another Δp range is se-
lected, the setting range is 2% ... 96% of the full scale value.
4
The value 300 Pa applies to the default setting of parameter T1 = 0 5000 Pa. If another Δp range is selected, the Δp hystere-
sis value is 6% of the full scale value.
5
The setting range 100 Pa … 4700 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another Δp range is se-
lected, the setting range is 2% ... 94% of the full scale value.
6
The setting range 0 4600 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another Δp range is selected,
the setting range is 0 ... 92% of the full scale value.
7
The value 2000 Pa applies to the default setting of parameter T1 = 0 5000 Pa. If another Δp range is selected, the Δp max.
alarm value is 40% of the full scale value.
8
The setting range 0 5000 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another Δp range is selected,
the setting range is 0 ... 100% of the full scale value.
Parameter code 3 = 4711
Parameter code 4 = known only to the manufacturer of the filter system
Parameter code 5 = known only to the manufacturer of the filter system