5.9 Parameter list
Code
Text in display, line 1 Meaning
setting
Setting range
age
—
Language of the display text
Parameter block C0-C3 "Service operating hours counter"
Service operating hours counter
Operating hours counter mode
Parameter block D0-D8 “Δp-controls“
1
0 = Function inactive
2
The value 1000 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another Δp range is selected, the Δp starting
value is 20% of the full scale value.
3
The setting range 100 Pa … 4800 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another Δp range is se-
lected, the setting range is 2% ... 96% of the full scale value.
4
The value 300 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another Δp range is selected, the Δp hystere-
sis value is 6% of the full scale value.
5
The setting range 100 Pa … 4700 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another Δp range is se-
lected, the setting range is 2% ... 94% of the full scale value.
6
The setting range 0 … 4600 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another Δp range is selected,
the setting range is 0 ... 92% of the full scale value.
7
The value 2000 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another Δp range is selected, the Δp max.
alarm value is 40% of the full scale value.
8
The setting range 0 … 5000 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another Δp range is selected,
the setting range is 0 ... 100% of the full scale value.
Parameter code 4 = known only to the manufacturer of the filter system
Parameter code 5 = known only to the manufacturer of the filter system