EasyManua.ls Logo

red lion C48C - Page 48

red lion C48C
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-42-
1. Verify programming of the user input parameter.1. User input not properly programmed.
OUTPUT WILL NOT RESET
1. Program User input to a maintained reset.1. User input reset mode set for momentary reset.
4. Check or replace output board.4. Defective output board.
UNIT COUNTS WHILE
RESET IS ACTIVATED
3. Check output board.3. Incorrect output board.
2. Check wiring.2. Improperly wired.
1. Install output board.1. Output board not installed.
OUTPUTS NOT WORKING
PRESCALER, PRESETS, OR
OUTPUT TIME VALUES CAN
BE VIEWED BUT NOT
CHANGED
2. Check “Front Panel Accessible Functions With Program
Disable” section of manual.
1. Verify programming of Access parameters.1. Front panel disabled.
2. Configure Snk/Src jumper.2. User Input Snk/Src jumper configured improperly.
1. Verify programming of User Input parameter.1. User input not properly programmed.
1. Check “Front Panel Accessible Functions With Program
Disable” section of the manual.
1. Front panel disabled.
PROCESS, BATCH, OR
TOTAL VALUES WILL NOT
RESET WHEN A MANUAL
RESET IS PERFORMED
CAN NOT ENTER INTO
PROGRAMMING
REMEDIESPOSSIBLE CAUSE
PROBLEMS
APPENDIX “C” - TROUBLESHOOTING (Cont’d)

Table of Contents

Related product manuals