-47-
Released 2018-01-12 Drawing No. LP0932
REGISTER
(4x)
REGISTER NAME LOW LIMIT HIGH LIMIT
FACTORY
SETTING
ACCESS COMMENTS
216 Load Serial Settings 0 1 0 Write *
0 = No change, 1 = Load Serial Settings;
* - will read 0
PID SETS
311 314 PID Set 1
311 Setpoint 1 (SP1) 1000
312 PID Set 1 Proportional band 1
999(.9)° or
9999 (process)
700 Read/Write 1 = 1 Display unit
313 PID Set 1 Integral time 0 9999 120 Read/Write 1 = 1 second
314 PID Set 1 Derivative time 0 9999 30 Read/Write 1 = 1 second
315 PID Set 1 Integration default 0 1000 0 Read/Write 1 = 0.1 % output power
321 324 PID Set 2 (same order as PID Set 1)
331 334 PID Set 3 (same order as PID Set 1)
341 344 PID Set 4 (same order as PID Set 1)
351 354 PID Set 5 (same order as PID Set 1)
361 364 PID Set 6 (same order as PID Set 1)
SLAVE ID
1001 N/A N/A
0x5058
(“PX”)
Read Only 0x5058 (“PX”)
1002 N/A N/A
0x5532
(“U2”)
Read Only 0x5532 (“U2”)
1003 N/A N/A
0x3020
(“0”)
Read Only 0x3020 (“0”)
1004 N/A N/A
model
dependent
Read Only
0x55<n> (“Un”) ‘n’ - 1st output;
‘0’(0x30) = No Card installed,
‘x’ (0x78) = any output option card installed
1005 N/A N/A
model
dependent
Read Only
0x<b><c>
<b>(2nd Output): ‘0’ (0x30) = No Card installed,
‘x’ (0x78) = any output option card installed
<c>(Options): ‘9’ = RS485/No User Inputs,
‘A’ = RS485/2 User Inputs
1006 N/A N/A
0x2020
(“ “)
Read Only 0x2020 (“ “)
1007 N/A N/A Read Only
0x0200 = Software database version number in BCD
(0x0200 = 2.00)
1008 N/A N/A 0x10 Read Only 0x10 = 16 reads
1009 N/A N/A 0x10 Read Only 0x10 = 16 writes
1010 N/A N/A 0 Read Only
SETPOINT PROFILE REGISTERS
1091
Profile Deviation Error Value
(Programmable Waiting
Temperature)
0 1000 0 Read/Write
1092
Profile Error Band Timeout
(Programmable Waiting Time)
0 900 0 Read/Write
1093
Profile Initial Ramp Rate
(Programmable Slope Increase)
10 Read/Write
1101 1612
Profile 0-15, Segment 0-15, Setpoint
Value (Odd number)
Profile 0-15, Segment 0-15 Segment
Time (Even number)
-999
Time: 0
9999
Time: 900 minutes
0 Read/Write
1631 1646
Profile 0-15 Number of Segments 0 15 15 Read/Write
1651 1666
Profile 0-15 Cycle Repeat 0 99 0 Read/Write
1671 1686
Profile 0-15 Link Profile 0 16 16 Read/Write