2 - INSTALLATION
EXTERNAL AIR INLET
It is mandatory to provide an adequate external air intake that supplies the combustion air required for the product to work properly. The
ow of air between the outside and the installation room may be direct, through an inlet in an external wall of the room; or indirect, via
air intake from adjoining rooms and connecting permanently with the installation room (see Figure 9 b). Adjoining areas may not include
sleeping areas, garages or general areas with a re hazard. During installation one must check the minimum clearances required for air
intake from outside. Take into account the presence of doors and windows that could interfere with the proper ow of air to the stove (see
diagram below).
The air inlet must have a minimum net total area of 80 cm2: the surface must be increased accordingly if there are other active generators
(for example: electric fan for stale air extraction, hood, other stoves, etc.), which could cause a depression in the room. Make sure that,
with all appliances on, the pressure drop between the room and the outside does not exceed 4 Pa (also for sealed appliances if the
combustion air has not been suitably ducted outside). If necessary increase the intake section of the air inlet, which must be made at oor
level and always protected with a bird-proof outer protection grid and in such a way that it cannot be obstructed by any object.
FIGURE 9 A - DIRECTLY FROM OUTSIDE
FIGURE 10
FIGURE 9 B - INDIRECTLY FROM THE ADJACENT ROOM
A=AIR INLET
B=ROOM TO BE VENTILATED
C=INCREASE OF THE GAP UNDER THE DOOR