EasyManua.ls Logo

Reflex variomat 2-2/60 - Page 14

Default Icon
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Designation
Terminal
Contactor
terminal
Signal Remarks
Pump 2
18 M2
(230 V)
19 N Is connected
20 PE
Pump 1 (2)
6K1 / 2 U
(400 V)
6K1 / 4 V
6K1 / 6 W
X0 / 6 PE
Pump 2
6K5 / 2 U
(400 V)
6K5 / 4 V
6K5 / 6 W
X0 / 7 PE
Overfl ow solenoid
valve 1 (5)
7Y2
8N
Is connected
9PE
Overfl ow solenoid
valve 2
10 Y3
Is connected11 N
12 PE
Motorised ball
valve 1
55 GND
56 +24 V
Supply
57 0 - 10 V Manipulated variable
58 0 - 10 V Feedback
Motorised ball
valve 2
51 GND
52 +24 V
Supply
53 0 - 10 V Manipulated variable
54 0 - 10 V Feedback
RS-485
The interface is positioned at the display board in the bottom
interface
left corner of the control box door. Description → p. 24
reflex ’variomat’
Assembly
14
Designation
Terminal Signal Remarks
Supply 1 PE
’variomat 1’ line wired with a shock-proof plug(230 V) 2 N
3L
Make-up (4) 10 Y1
(230 V) 11 N
12 PE
Common message 13 COM
(fl oating) 14 NC
15 NO
Level gauge 19 PE
Screen
(pressure cell) 20 - level Signal
(8) 21 + level + 18 V
Pressure
transducer (4)
22 PE
Screen
23 - pressure Signal
24 + pressure + 18 V
Pump 1 (2) 4 PE
(230 V) 5 N
6M1
Overfl ow solenoid
valve 1 (5)
7Y2
8N
Is connected
9PE
Overview of the wiring diagram on the circuit board - ’variomat 1’