When modifying parameters in User Mode or Lithium, the following rules must be followed to set
parameters successfully.
If setting the Low Voltage Disconnect in User Mode, it must always be at least 2V lower than
the Low Voltage Disconnect Recovery Voltage
Overvoltage Disconnect > Overvoltage Disconnect Recover ≥ Equalization voltage ≥ Boost voltage
≥ Float voltage
Overvoltage Disconnect > Over Voltage Disconnect Recover
Low Voltage Disconnect Recover > Low Voltage Disconnect (at least 2V Smaller) < Discharge
Limit Voltage
Undervoltage Recover > Undervoltage Alarm
NOTE