TECHNICAL INFORMATION
EN 303-1 7.2result
the required draught in mbar0.04 mbar
gas side resistance and combustion chamber pressure
for boilers operating with positive pressure in mbar
0.14 mbar
exit flue gas temperature in ℃140 ℃
exit flue gas mass flow in kg/s0.0088 kg/s
emissions of nitrogen oxides NOx in mg/kWh119 mg/kWh
exit flue connection diameter in mm75 mm
water resistance in mbar
20K - 60 mbar
10K - 80 mbar
maximum heat input in kW
19.6 kW
nominal heat output in kW18.5 kW
30 % nominal heat output in kW5.6 kW
useful efficiency at rated heat output and high
temperature regime in %
96 %
useful efficiency at 30 % of rated heat output and high
temperature regime in %
98 %
standby heat loss in kW0.089 kW
auxiliary electricity
consumption
at full load75 W
at part load40 W
in standby mode6 W
gas volume of the boiler in ㎥0.023 ㎥
range of temperature control in ℃(0 ~ 45) ℃
fuel typeDiesel
combustion chamber typeForced Exhaust
the combustion chamber dimensions and the
combustion chamber volume
0.015 ㎥
direct flame operation or flame reversalDirect flame
boiler type: ON/OFF, modulating, multi stageON/OFF