Air
Refrigerant Line Size Information
14AJM Series
38
Suction Line Length/Size versus Capacity Multiplier (R-410A)
Suction Line Run—Feet [m]
Optional
Standard
Optional
Optional
Standard
Optional
Optional
Standard
Optional
Optional
Standard
Optional
5 Ton4 Ton3
1
/2 Ton3 Ton2
1
/2 Ton2 TonUnit Size 1
1
/2 Ton
5
/8" [15.88 mm] O.D. Optional
3
/4" [19.05 mm] O.D. Standard*
3
/4" [19.05 mm] O.D. Optional
7
/8" [22.23 mm] O.D. Standard*
7
/8" [22.23 mm] O.D. Optional
1
1
/8" [28.58 mm] O.D. Standard*
25' [7.62]
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
50' [15.24]
.98
.99
.98
.99
.96
.98
.99
.98
.99
.99
.99
.99
.99
.99
.99
100' [30.48]
.95
.96
.95
.96
.94
.96
.97
.96
.97
.96
.98
.96
.98
.97
.98
150' [45.72]
.92
.93
.92
.94
.91
.93
.95
.94
.95
.94
.96
.95
.96
.94
.97
7/8" [22.23] I.D.Suction Line Connection Size 3/4" [19.05] I.D.
5
/8" [15.88 mm] O.D. Optional
3
/4" [19.05 mm] O.D. Standard*
7
/8" [22.23 mm] O.D. Optional
NOTES: *Standard line size
N/A = Application not recommended.
NOTES: *Standard line size
Using suction line larger than shown in chart will result in poor oil return and is not recommended.
3 Ton Suction Line Connection is 3/4"
[ ] Designates Metric Conversions
Condensing Unit Refrigerant Line Size Information