EasyManuals Logo

Rheem 90RS09EJS Series User Manual

Rheem 90RS09EJS Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
27
F
IGURE 18
ALTERNATE HORIZONTAL DIRECT VENT TERMINATION
Insulate the entire length of vent
pipe, between the elbow where the
pipe exits the wall and the elbow
where the termination is made, with
a
closed-cell insulation, such as
Arm-a-Flex” or “Rub-a-Tex” with a
minimum of 1/2” thickness.
All elbows installed on the exterior
of the building must be of the long
sweep nature.
As required for the horizontal piping
ran within the structure, any pipe
ran horizontal outside the structure
must slope upward a minimum of
1/4” per foot run so that condensate
drains toward the furnace.
From the top elbow in the exhaust
pipe, extend a length of PVC pipe
outward so that it terminates exactly
12 inches from the wall. See Figure
18. Reduce the termination pipe
extension to is 1
1
/2 inch pipe for
45,000 BTUH through 75,000 BTUH
units.
The 45,000 BTUH unit only uses kit
RXGY-D02. The 60,000 BTUH and
75,000 BTUH units may use kits
RXGY-D02 or RXGY-D03 depending
on pipe lengths and number of
elbows. Use kit RXGY-D03 with
90,000 BTUH through 120,000 BTUH
units. The RXGY-D04 kit only
applies to the 120,000 BTUH unit
using an alternate termination and
long runs. See Table 2.
The following are parts lists for the
RXGY-D02, RXGY-D03 and RXGY-
D04 alternate horizontal direct vent
termination kits:
RXGY-D02
1. 2-in. tee with reducer assembly
2.
1
/2-in. PVC 6-in. dia. trap
3. PVC vane
4. 2-in. PVC elbow
5. 1
1
/2-in. PVC nipple with coupling
6. PVC strap
7. vent template
RXGY-D03
1. 3-in. tee with reducer assembly
2.
1
/2-in. PVC 6-in. dia. trap
3. PVC vane
4. 2-in. PVC elbow
5. PVC strap
6. vent template
RXGY-D04
1. 2
1
/2-in. PVC elbow
2. 3" x 2
1
/2" PVC bushing
3. 2
1
/2" x 6
1
/2" long PVC pipe
4. 2
1
/2" x 16" long PVC pipe
5. 2
1
/2" x 21" long PVC pipe
6. PVC vane
7.
3-in. tee with reducer assembly
8. 6-in. dia.
1
/2-in. PVC trap
9. PVC strap
10. vent template
NOTE: The RXGY-D04 kit only
applies to the 120,000 BTUH unit
using an alternate termination and
excessively long runs.
S
EE DETAIL A
6
0 MAX.
P
IPE
S
UPPORT
S
TRAP
3 MAX.
NOTE: 3-1/2
M
AX. WHEN
D04 KIT IS
U
SED.
EXHAUST VENT
2
1
/2" PVC FOR MODELS WITH 120,000 BTU INPUT
(KIT NO. RXGY-D04)
2" PVC FOR MODELS WITH INPUTS OF 90,000 AND
120,000 BTU. REDUCE TO 1
1
/2" FOR MODELS WITH
INPUTS OF 45,000 THRU 60,000 BTU (SEE DETAIL A).
ELBOWS AND RISERS ARE 2" PVC.
I
NTAKE VENT
2
1
/2"
PVC FOR MODELS WITH
1
20,000 BTU INPUT.
2" PVC ELBOWS AND RISER
MODELS WITH INPUTS OF 45,000
THRU 120,000 BTU.
USE KIT NO. RXGY-D02 WHEN 2" PIPE
IS USED BETWEEN FURNACE AND
OUTSIDE WALL. USE KIT NO. RXGY-D03
WHEN 3" PIPE IS USED.
I339
1
2
F
R
OM
WA
L
L
3
4
EXHAUST
INTAKE
OPTIONAL
INTAKE
DETAIL B
EXHAUST / INTAKE RELATIONSHIP
DETAIL A
EXHAUST VENT FOR
MODELS WITH
I
NPUT OF 45,000 THRU
60,000 BTU
1
2
FR
O
M
WA
LL
1
1
/2 PIPE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rheem 90RS09EJS Series and is the answer not in the manual?

Rheem 90RS09EJS Series Specifications

General IconGeneral
BrandRheem
Model90RS09EJS Series
CategoryFurnace
LanguageEnglish

Related product manuals