17
VII. HEATER KIT CHARACTERISTICS
TABLE G (CONTINUED). AUXILIARY HEATER KITS CHARACTERISTICS AND APPLICATION
TABLE G (CONTINUED). (15, 20 & 25 TON MODELS)
MAX. FUSE
UNIT OR CKT. BKR.
MODEL HEATER KIT HEATER KIT UNIT MIN. CKT. SIZE (CKT. BKR.
NUMBER MODEL NO. HEATER KW FLA AMPACITY MUST BE
(-)LKB- RXJJ- HACR TYPE
FOR USA)
NONE* — — 114/114 125/125
CD20C 14.4/19.2 40.0/46.2 114/114 125/125
A300CL CD40C 28.8/38.4 79.9/92.4 119/134 125/150
CD60C 43.2/57.6 119.9/138.6 169/192 175/200
CD75C 54.0/72.0 149.9/173.2 206/235 225/250
NONE* — — 61 70
CD20D 19.2 23.1 61 70
A300DL CD40D 38.4 46.2 71 80
CD60D 57.6 69.3 100 100
CD75D 72.0 86.6 121 125
NONE* — — 43 50
CD20Y 19.2 18.5 43 50
A300YL CD40Y 38.4 37.0 57 60
CD60Y 57.6 55.4 80 80
CD75Y 72.0 69.3 97 100
NONE* — — 122/122 125/125
CD20C 14.4/19.2 40.0/46.2 122/122 125/125
A300CM CD40C 28.8/38.4 79.9/92.4 128/144 125/150
CD60C 43.2/57.6 119.9/138.6 178/202 200/225
CD75C 54.0/72.0 149.9/173.2 216/245 225/250
NONE* — — 62 70
CD20D 19.2 23.1 62 70
A300DM CD40D 38.4 46.2 72 80
CD60D 57.6 69.3 101 110
CD75D 72.0 86.6 123 125
NONE* — — 43 50
CD20Y 19.2 18.5 43 50
A300YM CD40Y 38.4 37.0 58 60
CE60Y 57.6 55.4 81 90
CD75Y 72.0 69.3 98 100