18
VII. HEATER KIT CHARACTERISTICS
TABLE G (CONTINUED). AUXILIARY HEATER KITS CHARACTERISTICS AND APPLICATION
TABLE G (CONTINUED). (15, 20 & 25 TON MODELS)
MAX. FUSE
UNIT OR CKT. BKR.
MODEL HEATER KIT HEATER KIT UNIT MIN. CKT. SIZE (CKT. BKR.
NUMBER MODEL NO. HEATER KW FLA AMPACITY MUST BE
(-)LMB- RXJJ- HACR TYPE
FOR USA)
NONE* — — 74/74 80/80
CD20C 14.4/19.2 40.0/46.2 74/74 80/90
A180CL CD40C 28.8/38.4 79.9/92.4 115/130 125/150
CD60C 43.2/57.6 119.9/138.6 165/183 175/200
CD75C 54.0/72.0 149.9/173.3 202/231 225/250
NONE* — — 43 45
CD20D 19.2 23.1 43 45
A180DL CD40D 38.4 46.2 67 70
CD60D 57.6 69.3 96 100
CD75D 72.0 86.6 117 125
NONE* — — 34 35
CD20Y 19.2 18.5 34 35
A180YL CD40Y 38.4 37.0 57 60
CD60Y 57.6 55.4 80 80
CD75Y 72.0 69.3 97 100
NONE* — — 77/77 80/80
CD20C 14.4/19.2 40.0/46.2 77/77 80/80
A180CM CD40C 28.8/38.4 79.9/92.4 119/134 125/150
CD60C 43.2/57.6 119.9/138.6 169/192 175/200
CD75C 54.0/72.0 149.9/173.2 206/235 225/250
NONE* — — 46 50
CD20D 19.2 23.1 46 50
A180DM CD40D 38.4 46.2 71 80
CD60D 57.6 69.3 100 110
CD75D 72.0 86.6 121 125
NONE* — — 34 35
CD20Y 19.2 18.5 34 35
A180YM CD40Y 38.4 37.0 57 60
CD60Y 57.6 55.4 80 80
CD75Y 72.0 69.3 97 100
NONE* — — 99/99 110/110
CD20C 14.4/19.2 40.0/46.2 99/99 110/110
A240CL CD40C 28.8/38.4 79.9/92.4 119/134 125/150
CD60C 43.2/57.6 119.9/138.6 169/192 175/200
CD75C 54.0/72.0 149.9/173.2 206/235 225/250
NONE* — — 57 60
CD20D 19.2 23.1 57 60
A240DL CD40D 38.4 46.2 71 80
CD60D 57.6 69.3 100 110
CD75D 72.0 86.6 121 125
NONE* — — 43 50
CD20Y 19.2 18.5 43 50
A240YL CD40Y 38.4 37.0 57 60
CD60Y 57.6 55.4 80 80
CD75Y 72.0 69.3 97 100
NONE* — — 107/107 110/110
CD20C 14.4/19.2 40.0/46.2 107/107 110/110
A240CM CD40C 28.8/38.4 79.9/92.4 128/144 125/175
CD60C 43.2/57.6 119.9/138.6 178/202 200/225
CD75C 54.0/72.0 149.9/173.2 216/245 225/300
NONE* — — 58 60
CD20D 19.2 23.1 58 60
A240DM CD40D 38.4 46.2 72 80
CD60D 57.6 69.3 101 110
CD75D 72.0 86.6 123 125
NONE* — — 43 50
CD20Y 19.2 18.5 43 50
A240YM CD40Y 38.4 37.0 58 60
CE60Y 57.6 55.4 81 90
CD75Y 72.0 69.3 98 100