16
ST-A1219-03-01
OUTDOOR UNIT ABOVE INDOOR SECTION LINE SET
REFERENCE TABLE 2
FOR ELEVATION
LIMITATIONS
INSULATE LIQUID AND
SUCTION LINE
VERIFY
SUB-COOLING
PRIOR TO
THROTTLING
DEVICE
TXV OR EEV AT INDOOR
EVAPORATOR
INSTALLATION
Interconnecting Tubing (cont�)
For applications that are considered to have a long
line set with the outdoor unit above the indoor unit
the following is required:
TXV at the indoor unit
Crankcase heater (some models have factory
installed CCH's� Refer to tables on pages 13 &
14)�
Start components maybe required depending
upon quality of voltage (consistently <200vac at
outdoor unit)
Insulated liquid and suction line in unconditioned
space only
Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments
spelled out in this document and the outdoor
units I&O
Verify at least 5°F sub-cooling at the ID unit prior
to throttling device
Tubing