AIR COOLED
CONDENSING UNITS
92-104921-09-07 (5/16)
Printed in USA
[ ] indicates metric conversions.
Do not destroy this manual.
Please read carefully
and keep in a safe place
for future reference by a
serviceman.
WARNING
THESE INSTRUCTIONS
ARE INTENDED AS AN AID
TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR
PROPER INSTALLATION,
ADJUSTMENT, AND
OPERATION OF THIS
UNIT. READ THESE
INSTRUCTIONS
THOROUGHLY
BEFORE ATTEMPTING
INSTALLATION OR
OPERATION. FAILURE
TO FOLLOW THESE
INSTRUCTIONS MAY
RESULT IN IMPROPER
INSTALLATION,
ADJUSTMENT, SERVICE,
OR MAINTENANCE
POSSIBLY RESULTING IN
FIRE, ELECTRICAL SHOCK,
PROPERTY DAMAGE,
PERSONAL INJURY, OR
DEATH.
INSTALLATION INSTRUCTIONS
(-)A13, (-)A14 & (-)A16 MODEL SERIES –
13, 14 & 16 SEER
WARNING:
RECOGNIZE THIS SYMBOL
AS AN INDICATION OF
IMPORTANT SAFETY
INFORMATION
ST-A1226-01-00
FEATURING INDUSTRY STANDARD
R-410A REFRIGERANT
earth friendly refrigerant
e
ar
t
h
r
y r
dly
dl
e
n
i
fr
h
NOTE: Actual unit appearance
may vary.

Table of Contents

Questions and Answers

  • W
    williamrodgersSep 23, 2025
    What causes a gurgling noise in my Rheem Air Conditioner's liquid line?
    • R
      Rebecca WhiteSep 23, 2025
      If you hear a gurgling or pulsing noise at the expansion device or liquid line of your Rheem Air Conditioner, it's likely due to air or noncondensibles in the system. To resolve this, recover the refrigerant, evacuate the system, and then recharge it.
  • G
    gallagherrichardAug 23, 2025
    Why are the registers sweating in my Rheem RA1430AJ1NA system?
    • W
      Walter GillAug 23, 2025
      If the registers in your Rheem Air Conditioner system are sweating, it's likely due to low indoor airflow. Try increasing the blower speed or reducing any restrictions in the airflow. Replacing the air filter can also help.
  • M
    mccanngregoryAug 25, 2025
    How to troubleshoot a Rheem RA1430AJ1NA Air Conditioner that will not run?
    • S
      Sean CarrAug 26, 2025
      If your Rheem Air Conditioner unit won't run, several factors could be the cause. It could be due to a power outage or loose electrical connection, so check the voltage at the line voltage connections. The thermostat might be out of calibration, so try resetting it. A blown fuse or tripped breaker can also prevent the unit from running, so replace the fuses or reset the breaker. Other potential issues include a defective transformer (check the wiring and replace if necessary), an open high-pressure control (reset it), an open low-pressure control, a defective control board (check diagnostic codes), or miswiring of communications (check communication wiring).
  • H
    hwagnerAug 27, 2025
    What to do if Rheem RA1430AJ1NA compressor short cycles?
    • H
      Harold ForbesAug 27, 2025
      If your Rheem Air Conditioner's compressor is short cycling, several factors could be responsible. First, check the voltage at the compressor terminals; it must be within ± 10% of the nameplate marking when the unit is operating. A defective overload protector could also be the cause, requiring replacement. Lastly, a refrigerant undercharge might be the issue, in which case you should add refrigerant.
  • J
    John HoldenAug 27, 2025
    What causes Rheem Air Conditioner outdoor fan to run but compressor not?
    • C
      Corey OneillAug 27, 2025
      If the outdoor fan of your Rheem Air Conditioner is running but the compressor isn't, it could be due to several reasons. A defective run or start capacitor may be the cause, requiring replacement. The contactor could also be defective and need replacement. Check for correct voltage at the compressor and ensure all connections are tight, as a loose connection could be the problem. The compressor might be stuck, grounded, have an open motor winding, or an open internal overload; wait at least 3 hours for the overload to reset, and if it remains open, replace the compressor. A low-voltage condition could also be the cause, in which case you should add start kit components.
  • H
    Hector ObrienSep 16, 2025
    What does it mean when my Rheem RA1430AJ1NA Air Conditioner has high head and low vapor pressures?
    • B
      Brittany ClaySep 16, 2025
      If your Rheem Air Conditioner has high head pressure but low vapor pressures, there might be a restriction in the liquid line, expansion device, or filter drier. Remove or replace the defective component. Another cause could be a bad TXV, which would need to be replaced.
  • J
    Jeffrey CarpenterSep 13, 2025
    Why is the indoor coil of my Rheem Air Conditioner iced, with low vapor pressure?
    • J
      Jeffrey RodriguezSep 13, 2025
      If you notice low vapor pressure, a cool compressor, and an iced indoor coil in your Rheem Air Conditioner, it could be due to low indoor airflow. Try increasing the blower speed or reducing restrictions, and replace the air filter. If you're operating the unit below 65°F outdoors, consider adding a Low Ambient Kit. Moisture in the system can also cause this issue, so recover the refrigerant, evacuate, recharge, and add a filter drier. Finally, a closed ID circuit could be the problem, requiring repair or replacement of the ID coil.
  • S
    Sheri JacksonSep 15, 2025
    What causes fluctuating head and vapor pressures in a Rheem RA1430AJ1NA Air Conditioner?
    • S
      Shelly CohenSep 15, 2025
      If your Rheem Air Conditioner is experiencing fluctuating head and vapor pressures, it could be due to TXV hunting. Check the TXV bulb clamp and air distribution on the coil; consider replacing the TXV. Another potential cause is air or noncondensibles in the system, which requires recovering the refrigerant, evacuating, and recharging.
  • S
    stoutaustinSep 5, 2025
    Why do my Rheem RA1430AJ1NA Air Conditioner registers sweat?
    • C
      Christian SharpSep 5, 2025
      Sweating registers in your Rheem Air Conditioner system are typically caused by low indoor airflow. To resolve this, increase the speed of the blower or reduce any restrictions. Also, replace the air filter.
  • L
    lauraclarkSep 3, 2025
    What does low head and high vapor pressures mean for Rheem RA1430AJ1NA Air Conditioner?
    • S
      Shawn BrownSep 3, 2025
      Low head pressure coupled with high vapor pressures in your Rheem Air Conditioner can point to a bad TXV, which requires replacement. Another potential cause is a bad compressor, which would also need replacing.

Summary

IMPORTANT SAFETY INFORMATION

Safety Warnings and Precautions

Key warnings for installation, operation, and electrical safety to prevent injury or death.

INSTALLATION: Choosing a Location

Location Considerations

Guidance on selecting an outdoor unit location for longevity and service.

Interconnecting Tubing: General

Interconnecting Tubing: Configuration - Outdoor Below Indoor

Interconnecting Tubing: Configuration - Outdoor Above Indoor

WIRING: Diagrams and Control Wiring

WIRING: Power Wiring and Grounding

START-UP Procedures

Initial Unit Start-Up

Steps for initial start-up, including crankcase heater energization.

Checking Airflow

Importance of proper airflow and how to measure it for system performance.

START-UP: Evacuation and Leak Testing

Evacuation Procedure

Detailed steps for evacuating the system to remove air and moisture.

Final Leak Testing

Methods for detecting leaks after evacuation using a halogen leak detector.

START-UP: Refrigerant Charge Verification

R-410 A Refrigerant Charging

Procedures for charging R-410A systems, including cautions and important notices.

Confirm Indoor Airflow and Coils

Ensuring proper indoor airflow and clean coils before adjusting refrigerant charge.

START-UP: Refrigerant Charge Adjustment

Gross Charging by Pressures

Procedure for gross charging based on system pressures and outdoor ambient temperature.

Final Charge by Subcooling

Method for fine-tuning the charge using subcooling values for optimal performance.

START-UP: Finishing Installation

DIAGNOSTICS

Electrical Checks Flowchart

Flowchart for diagnosing electrical issues in the air conditioning system.

Cooling Mechanical Checks Flowchart

General Troubleshooting Chart

Service Analyzer Charts: Compressor Overheating

Compressor Overheating Symptoms

Troubleshooting guide for compressor overheating issues and possible causes.

Service Analyzer Charts: Electrical and Flooded Starts

Electrical Troubleshooting

Diagnosing electrical problems like voltage issues, capacitor failures, and wiring faults.

Service Analyzer Charts: Contamination and Lubrication

Contamination Issues

Troubleshooting for system contamination due to moisture, noncondensibles, or debris.

Loss of Lubrication Problems

Diagnosing and fixing issues related to compressor lubrication, such as slugging.

Service Analyzer Charts: Flooding and TXV

Flooding Symptoms

Troubleshooting symptoms of refrigerant flooding and poor system control using TEV.

Thermostatic Expansion Valve (TEV) Issues

Diagnosing and resolving problems with TEV operation, including freezing and blockage.

Service Analyzer Charts: TEV Regulation

TEV Regulation Problems

Addressing issues where the TEV does not regulate properly, affecting superheat and suction.

Cooling Mode Troubleshooting Tips

WIRING DIAGRAMS: Single-Phase

WIRING DIAGRAMS: Three-Phase

Rheem RA1430AJ1NA Specifications

General IconGeneral
TypeSplit System Air Conditioner
SEER Rating14
HSPF RatingNot Applicable
Voltage208/230V
Phase1
Frequency60 Hz
RefrigerantR-410A
Compressor TypeScroll
Cooling Capacity30000 BTU
Operating Range (Cooling)55°F to 125°F